Fire And Life Safety Analysis- Building 310- The Landing, Tyler Paller
Fire And Life Safety Analysis- Building 310- The Landing, Tyler Paller
Fire Protection Engineering: Culminating Experience Project Reports
The purpose of this report is to analyze Building 310 with regards to fire and life safety. Analysis was done both prescriptively and from a performance based design standpoint. The prescriptive based analysis includes review of the building’s design with regards to egress, fire alarm systems, suppression systems, and structural fire protection. The building was reviewed against current NFPA codes and the International Building Code to examine compliance. The performance-based analysis consists of two different fire scenarios that were examined. The goal was to show that the building met safety criteria and does not pose undue risk to occupants. This …
Fire Protection Analysis Robert And Margrit Modavi Center For The Performing Arts- Uc Davis, Jeffrey Paterson
Fire Protection Analysis Robert And Margrit Modavi Center For The Performing Arts- Uc Davis, Jeffrey Paterson
Fire Protection Engineering: Culminating Experience Project Reports
This document is the report of the culminating experience as part of the master’s program in fire protection engineering at the California Polytechnic State University, San Luis Obispo. This report contains a life safety analysis of the fire protection systems of a chosen project building. The building examined is the Robert and Margrit Mondavi Center for the Performing Arts, located on the University of California Davis campus. The building was constructed in 2002 where the first performance occurred in October 2002. A large portion of the report applies prescriptive code requirements to evaluate compliance with current codes and standards. The …
Hotel- Georgia, Rock Toler
Hotel- Georgia, Rock Toler
Fire Protection Engineering: Culminating Experience Project Reports
The State of Georgia modifies the International Building Code through State amendments, to require a fire resistance rating between residential occupancies and all other occupancies. This fire and life safety analysis report will substantiate the necessity for the barrier in a mixed-use hotel occupancy. The first-half of the report addresses the prescriptive-based code requirements, reporting a compliant design was presented. Then the performance portions primary objective was established, maintain a tenable environment for egressing guest room occupants. Three conditions were evaluated to define a tenable environment, carbon monoxide levels, temperature, and visibility limits. Selecting the location of the fire required …
Comprehensive Fire And Life Safety Analysis- Moa Public Works Building- Anchorage, Alaska, Andrew J. Bigalke
Comprehensive Fire And Life Safety Analysis- Moa Public Works Building- Anchorage, Alaska, Andrew J. Bigalke
Fire Protection Engineering: Culminating Experience Project Reports
This report is a Comprehensive Fire and Life Safety Analysis addressing both prescriptive and performance based engineering analysis of the MOA Public Works building located in the Municipality of Anchorage, Alaska. The Public Works building was originally built in 1997 under the code requirements of the Uniform Building Code, as a Type II-N building. An addition was constructed in 2002 using the International Building Code (IBC), 2000 Edition. A prescriptive analysis is performed using the requisite building code and standards currently adopted by the State of Alaska, and by the Municipality of Anchorage. The currently adopted building codes and standards …
Fire And Life Safety Analysis- Cal Poly Recreation Center, Connor Mcgill
Fire And Life Safety Analysis- Cal Poly Recreation Center, Connor Mcgill
Fire Protection Engineering: Culminating Experience Project Reports
The purpose of this fire and life safety analysis is to determine whether Cal Poly’s Recreation Center meets fire safety goals. The primary fire safety goal is to provide building occupants with an environment that is tenable and allows for safe egress in the event of a fire, and reduce the likelihood of any catastrophic fire event. This goal can be achieved by protecting the occupants not intimate with the initial fire development and improving survivability of those occupants intimate with the initial fire development, NFPA 101, 2012. A prescriptive-based design approach and a performance-based design approach are used to …
Fire Protection And Life Safety Analysis- Dell Medical School Academic Building, David Gramlich
Fire Protection And Life Safety Analysis- Dell Medical School Academic Building, David Gramlich
Fire Protection Engineering: Culminating Experience Project Reports
This report is on the Dell Medical School Academic Building located in Austin, Texas. The life safety and prescriptive based code requirements are summarized within this report. It also includes conceptual fire protection and fire alarm system design. This report mentions University of Texas System Owner’s Design Guidelines that exceed the required code requirements. This report was developed when the building was in the Design Development stage. Since, code deficiencies have been addressed, and changes have been made to the building during the remainder of the design process, this report does not reflect the actual construction or protection strategies used …
Construction Warehouse, Ben Johnson
Construction Warehouse, Ben Johnson
Fire Protection Engineering: Culminating Experience Project Reports
The purpose of this report is to provide a comprehensive evaluation of the fire protection and life safety design of a warehouse building that serves a large construction project. The results and conclusions from this evaluation are documented herein and supported by analysis when necessary. The gross floor area per story of the construction warehouse is 39,000 ft2. This building is used as a warehousing facility in support of a large construction project. Rack storage of Group A plastics is permitted in this facility to a height of 20 ft. beneath a 24 ft. ceiling on the main floor. Shelf …
Orangeburg Assembly Hall Of Jehovah's Witnesses- Fire Protection And Life Safety Design Analysis, Justin B. Biller
Orangeburg Assembly Hall Of Jehovah's Witnesses- Fire Protection And Life Safety Design Analysis, Justin B. Biller
Fire Protection Engineering: Culminating Experience Project Reports
In partial fulfillment of the requirements for the Degree of Masters of Science in Fire Protection Engineering, a prescriptive and performance-based engineering analysis was performed on the Orangeburg Assembly Hall of Jehovah’s Witnesses. The building was recently constructed and completed in 2013 in Orangeburg, South Carolina to serve as a center for education of Jehovah’s Witnesses on Biblical principles for daily life. More than 300 congregations throughout Georgia and the Carolinas will use the Assembly Hall for their semi-annual assemblies and conventions, with an estimated annual attendance of 190,000 per year. Prescriptive analyses were conducted based primarily upon the provisions …
Fire Protection Life Safety Analysis- Bachelor Enlisted Quarters, Kyle C. Leadon
Fire Protection Life Safety Analysis- Bachelor Enlisted Quarters, Kyle C. Leadon
Fire Protection Engineering: Culminating Experience Project Reports
This Bachelor Enlisted Quarters (BEQ) shall be constructed, arranged, equipped, maintained, and operated in accordance with this report and applicable criteria to ensure a minimum level of life safety and property protection is provided from actual and potential fire hazards. The goal is to ensure the occupants are provided with an environment that is reasonably safe from fire. We accomplish this goal by protecting occupants not intimate with the initial fire development, and by improving the survivability of occupants intimate with the initial fire development. The protection described in this report takes on many forms, from active protection, such as …
Mixed‐Use Commercial And Residential Podium Building, Gene Voloshenko
Mixed‐Use Commercial And Residential Podium Building, Gene Voloshenko
Fire Protection Engineering: Culminating Experience Project Reports
This report provides a summary of the principal fire protection and life safety features for a mixed use commercial and residential Podium Building for compliance with the 2000 International Building Code (IBC) and the 2003 NFPA 101 “Life Safety Code”. IBC permits compliance with the prescriptive Code requirements using Alternative Solutions that will achieve at least the minimum level of performance required by the IBC as defined by the objectives and functional statements and as described in the NFPA 101 Chapter 5. Alternative solutions for this project were modeled using the Fire Dynamics Simulator (FDS). One of the primary recommendations …
Fire Protection Analysis Of A Fresno Elementary School, Garen Lencioni
Fire Protection Analysis Of A Fresno Elementary School, Garen Lencioni
Fire Protection Engineering: Culminating Experience Project Reports
This report details the fire and life safety analysis of a Fresno Elementary School. Both prescriptive and performance based analysis were used to determine compliance with the building codes and fire codes which the building was constructed under. The prescriptive analyses included evaluation of the egress system, structural fire protection requirements, fire detection and alarm system and fire suppression systems. The prescriptive analyses were done to show the code requirements and how the building complies with them. The performance analyses were done to analyze the performance of the building in the event of a fire scenario. Three fire scenarios were …
Fire Protection Analysis Of The ‘Center For The Arts’ Building', Steven W. Carman
Fire Protection Analysis Of The ‘Center For The Arts’ Building', Steven W. Carman
Fire Protection Engineering: Culminating Experience Project Reports
In partial fulfillment of the requirements for the Degree of Masters of Science in Fire Protection Engineering, a prescriptive and performance-based analysis was performed on a building housing the Center for the Arts. The building was constructed in 1947 in California as an automobile dealership and repair shop under the provisions of the then-controlling Uniform Building Code. It subsequently underwent several occupancy changes and has since served as a beauty school, gymnastics center, and currently as a performing and visual arts center. Prescriptive analyses were conducted based primarily upon the provisions of the 2010 California Building and Fire Codes, and …
Adams 14 High School Life Safety Report, Todd L. Brand
Adams 14 High School Life Safety Report, Todd L. Brand
Fire Protection Engineering: Culminating Experience Project Reports
The purpose of this Life Safety Report (LSR) is to provide a prescriptive based analysis of the Adam County High School based on the existing codes that the building was constructed under. This will include exterior and interior building construction, fire protection systems, and egress requirements. Additionally, this report will evaluate selected performance based design scenarios for the High School. Findings and recommendations to the performance based design scenarios, along with any deficiencies, are noted at the conclusion of the report. The prescriptive analysis of this report will focus on the International Building Code requirements with emphasis on Chapters 4 …
Robert E. Kennedy Library Cal Poly, San Luis Obispo Fire Protection Analysis Fpe Culminating Project, Isaac De Haro Martinez
Robert E. Kennedy Library Cal Poly, San Luis Obispo Fire Protection Analysis Fpe Culminating Project, Isaac De Haro Martinez
Fire Protection Engineering: Culminating Experience Project Reports
California State University has acquired fire protection services to conduct a survey of and produce a fire protection report that analyzes the current condition of the existing Robert E. Kennedy Library on the Cal Poly campus. The prescriptive analysis of the Library is based on the 2010 California Building- the analysis considers the building a new building and will not consider the building provision for existing buildings as permitted by Chapter 34 of the CBC. A performance-based design using FDS is also analyzed to determine the tenability advantages of providing fire sprinklers within the Library. Non-conforming conditions include, among others, …
Court House Project- Fire Protection Report, Ryan Rigsbee
Court House Project- Fire Protection Report, Ryan Rigsbee
Fire Protection Engineering: Culminating Experience Project Reports
This fire protection report intends to provide Fictitious Architects (The Client) with sufficient information about code requirements and best practices pertaining to occupant and building safety. The chapters within this report include specific design requirements to aid the client during the design of the Court House Project. The following recommendations have been prepared by Ryan Rigsbee to address all major building code requirements for life safety systems. These life safety systems include egress, fire alarm and signaling, water-based fire suppression, structural fire protection, smoke control, and an emergency management plan. This project details the requirements for a new courthouse containing …
Bulding 192, Engineering Iv, Cal Poly, San Luis Obispo, Mark Ferraresi
Bulding 192, Engineering Iv, Cal Poly, San Luis Obispo, Mark Ferraresi
Fire Protection Engineering: Culminating Experience Project Reports
This report presents a fire and life safety analysis of Engineering IV. This analysis includes a review of prescriptive code requirements per the International Building Code, 2009 Edition and other applicable codes and standards; a description of the current fire and life safety systems or features in place; a prescriptive.based analysis; and a performance.based analysis. Beyond typical fire protection systems, such as means of egress systems and structural fire protection, Engineering IV was found to an automatic fire alarm and notification system, an automatic sprinkler system, and smoke control features. The systems and features surveyed were found to be within …
Fire And Life Safety Analysis Of The Performing Arts Center's Christopher Cohan Center, David Phillips
Fire And Life Safety Analysis Of The Performing Arts Center's Christopher Cohan Center, David Phillips
Fire Protection Engineering: Culminating Experience Project Reports
This report is a review of the fire protection systems installed in the Christopher Cohan Center on the Cal Poly, San Luis Obispo campus. The systems reviewed are the passive structural fire protection, passive and active egress components, and active detection and suppression systems. The report examines whether the reviewed systems in the building meet the prescriptive requirements of the 2010 California Building Code(CBC) and California Fire Code(CFC). The building will be further subjected to a performance based analysis. Two design fire scenarios are presented, and an analysis of available safe egress time (ASET) is compared with an analysis of …
Fire Protection Analysis Of The Orfalea College Of Business Building (#3), William Fletcher
Fire Protection Analysis Of The Orfalea College Of Business Building (#3), William Fletcher
Fire Protection Engineering: Culminating Experience Project Reports
A performance and prescriptive based analysis was performed on the Orfalea College of Business Building (#3) on Cal Poly’s Campus. The building was originally designed to meet the 1985 Uniform Building Code (UBC). The building’s original design and current existing condition will be examined. The business building will be evaluated using the California Building Code, California Fire Code, NFPA 101 Life Safety code and other relevant NFPA Codes. The fire protection systems will be separated and evaluated into systems by Egress Components, Fire Alarm and Detection, Water- Based Suppression and Structural Fire Protection. The combined interactions of the systems are …