Full-Text Articles in Entire DC Network

Investigation On The Regeneration And Corrosion Characteristics Of An Anodized Aluminum Plate Regenerator., Tao Wen, Lin Lu, Hongxing Yang, Yimo Luo Jan 2018

Investigation On The Regeneration And Corrosion Characteristics Of An Anodized Aluminum Plate Regenerator., Tao Wen, Lin Lu, Hongxing Yang, Yimo Luo

Faculty of Science & Technology (THEi)

The traditional vapor compression cooling system (VCS) has been criticized for its heavy reliance on electricity consumption and limited control ability of humidity. Compared with the VCS, the liquid desiccant cooling system (LDCS) is more efficient by handling the sensible and latent load separately. The present study investigated the regeneration and corrosion characteristics of an anodized aluminum plate regenerator for the first time. Comparative tests were conducted to present the regeneration and corrosion characteristics of the normal and anodized regenerator. The influence of internal heating on the regeneration performance was also identified. The results showed that the corrosion rate was …


Investigation On The Regeneration Performance Of Liquid Desiccant By Adding Surfactant Pvp-K30., Tao Wen, Lin Lu, Chuanshuai Dong, Yimo Luo Jan 2018

Investigation On The Regeneration Performance Of Liquid Desiccant By Adding Surfactant Pvp-K30., Tao Wen, Lin Lu, Chuanshuai Dong, Yimo Luo

Faculty of Science & Technology (THEi)

The liquid desiccant cooling system (LDCS) is a promising alternative for the conventional vapor compression system due to its high energy efficiency. To enhance the mass transfer between the regeneration air and liquid desiccant in the regenerator, the paper firstly introduced a kind of surfactant called polyvinyl pyrrolidone (PVP-K30) which was added into the LiCl solution for better desiccant regeneration performance. The falling film characteristics and regeneration performance were investigated and compared with and without surfactant. The results indicated that the contact angle of desiccant solution on plate decreased from 58.5° to 28.0° by adding surfactant with 0.4% of concentration. …


A Parameter Study Of The Effect Of A Plasma-Induced Ozone Colour-Fading Process On Sulphur-Dyed Cotton Fabric, Dan Zhong, Yao Hui Liu, Ngan Ting Cheung, Chi Wai Kan, Hong Chua Jan 2018

A Parameter Study Of The Effect Of A Plasma-Induced Ozone Colour-Fading Process On Sulphur-Dyed Cotton Fabric, Dan Zhong, Yao Hui Liu, Ngan Ting Cheung, Chi Wai Kan, Hong Chua

Faculty of Science & Technology (THEi)

A plasma-induced ozone colour-fading treatment was used for treating a blue sulphur-dyed knitted cotton fabric. Since the process parameters of plasma-induced ozone colour-fading treatment are inter-related with one other, the final colour-fading results are affected. An orthogonal array testing strategy (OATS) method was used for determining the optimum conditions of the plasmainduced ozone colour-fading treatment in this study. Three process parameters used in the plasmainduced ozone colour-fading treatment, i.e., oxygen gas concentration (%), water content in fabric (%), and treatment time (minutes), were used in the optimization process. Experimental results reveal the optimum conditions for fading the colour by plasma-induced …


A New Capacity Controller For A Direct Expansion Air Conditioning System For Operational Safety And Efficiency., Yudong Xia, Huaxia Yan, Shiming Deng, Ming-Yin Chan Jan 2018

A New Capacity Controller For A Direct Expansion Air Conditioning System For Operational Safety And Efficiency., Yudong Xia, Huaxia Yan, Shiming Deng, Ming-Yin Chan

Faculty of Science & Technology (THEi)

For achieving a balance between the operational safety and efficiency of a variable speed direct expansion air conditioning system, a new capacity controller that can not only simultaneously control indoor air temperature and humidity, but also select an optimized degree of superheat setting to properly balance the operational safety and efficiency has been developed, by adding a control module to a previously developed capacity controller. The core of the control module was an artificial neural network based model representing the known relationship between the inherent operational characteristics and operational stability of a variable speed direct expansion air conditioning system. Using …


Investigation On Solar Assisted Liquid Desiccant Dehumidifier And Evaporative Cooling System For Fresh Air Treatment., Yi Chen, Hongxing Yang, Yimo Luo Jan 2018

Investigation On Solar Assisted Liquid Desiccant Dehumidifier And Evaporative Cooling System For Fresh Air Treatment., Yi Chen, Hongxing Yang, Yimo Luo

Faculty of Science & Technology (THEi)

The widely used semi-centralized air conditioning (A/C) system consisting of independent fresh air system and fan coil system suffers from huge energy consumption, especially for fresh air treatment. Therefore, a liquid desiccant dehumidifier and regenerative indirect evaporative cooling (LDD-RIEC) system is proposed for fresh air treatment. The fresh air is handled by the LDD-RIEC system in which no electricity-intensive compressor involves. The hot and humid fresh air is firstly dehumidified by LDD and then sensibly cooled by RIEC. The thermal energy captured by solar collectors is used for desiccant solution regeneration. Indoor return air is cooled by fan coils of …


Development And Experimental Study Of A Novel Plate Dehumidifier Made Of Anodized Aluminum., Tao Wen, Lin Lu, Chuanshuai Dong, Yimo Luo Jan 2018

Development And Experimental Study Of A Novel Plate Dehumidifier Made Of Anodized Aluminum., Tao Wen, Lin Lu, Chuanshuai Dong, Yimo Luo

Faculty of Science & Technology (THEi)

The falling film dehumidifier is a key component in the liquid desiccant cooling system (LDCS). However, the most commonly used metals, such as steel and aluminum, can hardly resist the erosion of liquid desiccant. It greatly limits the fabrication of compact dehumidifiers and hinders the promotion of LDCS. The present study introduced a novel falling film dehumidifier which was made by the metal of anodized aluminum. Experiments were carried out to compare the dehumidification performance between ordinary aluminum dehumidifier and anodized one. The influences of air temperature, mass flow rate, inlet humidity and solution temperature, mass flow rate, temperature on …


Further Development Of A Thermal Comfort Based Fuzzy Logic Controller For A Direct Expansion Air Conditioning System, Huaxia Yan, Yan Pan, Zhao Li, Shiming Deng Jan 2018

Further Development Of A Thermal Comfort Based Fuzzy Logic Controller For A Direct Expansion Air Conditioning System, Huaxia Yan, Yan Pan, Zhao Li, Shiming Deng

Faculty of Science & Technology (THEi)

The primary purpose of A/C is offering occupants with acceptable indoor thermal comfort levels. Thermal comfort is a complicated result of non-linear interactions between six parameters. However, many of current A/C systems solely control air temperature. Whenever anyone of the five parameters other than temperature varies significantly, an occupant may feel thermally uncomfortable. To address the issue, a comprehensive thermal comfort index should be used as regulator in A/C systems. One fuzzy logic controller is available. However, the approach to the fuzzy logic controller is complicated. In this paper, one previous established fuzzy logic controller is simplified for its real …


Energy Performance Of Solar Assisted Desiccant Enhanced Evaporative Cooling Air Conditioning Ssystem, Yi Chen, Weichen Yu, Peishi Wu, Hongxing Yang, Yimo Luo Jan 2017

Energy Performance Of Solar Assisted Desiccant Enhanced Evaporative Cooling Air Conditioning Ssystem, Yi Chen, Weichen Yu, Peishi Wu, Hongxing Yang, Yimo Luo

Faculty of Science & Technology (THEi)

The desiccant enhanced evaporative cooling system is proposed as a promising energy-saving air-conditioning (A/C) scheme. It consists of hybrid liquid desiccant dehumidifier and indirect evaporative cooler. The hot and humid air is firstly dehumidified by liquid desiccant dehumidifier (LDD) and then sensibly cooled by regenerative indirect evaporative cooler (RIEC). The LDD-RIEC system operates without electricity-intensive compressor but with low-power-consumption solution pumps and water pumps. The heat captured by the solar collector is used for regenerating the desiccant solution. The solar collector model, LDD model and RIEC model were established separately to facilitate the hybrid system simulation in a closed-loop. The …


Making Marble Powder Waste Profitable By Using Nano-Tio2 Surface Modification For Air Quality Improvement Applications, Yaxiong Ji, Xing Rong, Hong Zhong, Yuanhao Wang, Shifeng Wang, Lin Lu Jan 2017

Making Marble Powder Waste Profitable By Using Nano-Tio2 Surface Modification For Air Quality Improvement Applications, Yaxiong Ji, Xing Rong, Hong Zhong, Yuanhao Wang, Shifeng Wang, Lin Lu

Faculty of Science & Technology (THEi)

We report a brand new recycling route of waste marble powder, by means of surface modification with homemade nano-TiO2 particles to produce low cost coating materials for the application in air quality improvement. The as-prepared nano-TiO2 in anatase phase exhibits excellent photocatalytic characteristic, reflected by the high degradation rate of over 95% of methylene blue within 6 hours of UV irradiation. The prepared coating consisting of nano-TiO2 clad marble powder was tested by monitoring the decomposition rate of formaldehyde gas. A high degradation efficiency of about 95% within 9 hours of illumination is achieved, demonstrating a promising potential for removing …