Further Development Of A Thermal Comfort Based Fuzzy Logic Controller For A Direct Expansion Air Conditioning System, Huaxia Yan, Yan Pan, Zhao Li, Shiming Deng Jan 2018

Further Development Of A Thermal Comfort Based Fuzzy Logic Controller For A Direct Expansion Air Conditioning System, Huaxia Yan, Yan Pan, Zhao Li, Shiming Deng

Faculty of Science & Technology (THEi)

The primary purpose of A/C is offering occupants with acceptable indoor thermal comfort levels. Thermal comfort is a complicated result of non-linear interactions between six parameters. However, many of current A/C systems solely control air temperature. Whenever anyone of the five parameters other than temperature varies significantly, an occupant may feel thermally uncomfortable. To address the issue, a comprehensive thermal comfort index should be used as regulator in A/C systems. One fuzzy logic controller is available. However, the approach to the fuzzy logic controller is complicated. In this paper, one previous established fuzzy logic controller is simplified for its real …


Experimental Study Of A Novel Subcooling Method Based On Liquid Desiccant Dehumidification For Vapor-Compression Refrigeration Systems., Xiaohui She, Yonggao Yin, Yimo Luo, Lindeman Brett, Dan Zhong, Xiaosong Zhang Jan 2018

Experimental Study Of A Novel Subcooling Method Based On Liquid Desiccant Dehumidification For Vapor-Compression Refrigeration Systems., Xiaohui She, Yonggao Yin, Yimo Luo, Lindeman Brett, Dan Zhong, Xiaosong Zhang

Faculty of Science & Technology (THEi)

Refrigerant subcooling could increase the refrigerating capacity and potentially improve the performance of refrigeration systems. In this paper, a novel subcooling method is experimentally studied for the first time in a hybrid vapor compression refrigeration system. In this system, condensation heat (~40 °C) is used to drive an integrated subcooling cycle to subcool the refrigerant leaving the condenser, which significantly increases the system performance. Changes in system performance are measured as functions of the following variables: the mass flow rates of the dehumidification air, ambient air, dehumidification solution, regeneration solution, and spraying water. Comparisons are made between the proposed system …


Investigation On The Regeneration Performance Of Liquid Desiccant By Adding Surfactant Pvp-K30., Tao Wen, Lin Lu, Chuanshuai Dong, Yimo Luo Jan 2018

Investigation On The Regeneration Performance Of Liquid Desiccant By Adding Surfactant Pvp-K30., Tao Wen, Lin Lu, Chuanshuai Dong, Yimo Luo

Faculty of Science & Technology (THEi)

The liquid desiccant cooling system (LDCS) is a promising alternative for the conventional vapor compression system due to its high energy efficiency. To enhance the mass transfer between the regeneration air and liquid desiccant in the regenerator, the paper firstly introduced a kind of surfactant called polyvinyl pyrrolidone (PVP-K30) which was added into the LiCl solution for better desiccant regeneration performance. The falling film characteristics and regeneration performance were investigated and compared with and without surfactant. The results indicated that the contact angle of desiccant solution on plate decreased from 58.5° to 28.0° by adding surfactant with 0.4% of concentration. …


Investigation On The Regeneration And Corrosion Characteristics Of An Anodized Aluminum Plate Regenerator., Tao Wen, Lin Lu, Hongxing Yang, Yimo Luo Jan 2018

Investigation On The Regeneration And Corrosion Characteristics Of An Anodized Aluminum Plate Regenerator., Tao Wen, Lin Lu, Hongxing Yang, Yimo Luo

Faculty of Science & Technology (THEi)

The traditional vapor compression cooling system (VCS) has been criticized for its heavy reliance on electricity consumption and limited control ability of humidity. Compared with the VCS, the liquid desiccant cooling system (LDCS) is more efficient by handling the sensible and latent load separately. The present study investigated the regeneration and corrosion characteristics of an anodized aluminum plate regenerator for the first time. Comparative tests were conducted to present the regeneration and corrosion characteristics of the normal and anodized regenerator. The influence of internal heating on the regeneration performance was also identified. The results showed that the corrosion rate was …


Inherent Operational Characteristics Aided Fuzzy Logic Controller For A Variable Speed Direct Expansion Air Conditioning System For Simultaneous Indoor Air Temperature And Humidity Control., Huaxia Yan, Yudong Xia, Xiangguo Xu, Shiming Deng Jan 2018

Inherent Operational Characteristics Aided Fuzzy Logic Controller For A Variable Speed Direct Expansion Air Conditioning System For Simultaneous Indoor Air Temperature And Humidity Control., Huaxia Yan, Yudong Xia, Xiangguo Xu, Shiming Deng

Faculty of Science & Technology (THEi)

Direct expansion air conditioning systems are widely installed in small-to medium- scale buildings due to their advantages of simple configuration, high energy efficiency and low cost to own and maintain. The two main targets of air conditioning operation include improving the system operational efficiency and energy efficiency. Stable system operational efficiency is directly related with the operation of electronic expansion valves and degree of superheat at the outlet of evaporator. In this paper, an adaptive DS controller is developed to improve the system operational efficiency based the experimental performance of a DX A/C system and reported. The adaptive DS controller …