Underground Lrt Station- Final Project, Itay Mesika Jun 2025

Underground Lrt Station- Final Project, Itay Mesika

Fire Protection Engineering: Culminating Experience Project Reports

This project presents a comprehensive fire protection analysis for an underground light rail transit (LRT) station that also serves as a civil defense shelter. The station comprises two underground levels with a total area of 4,500 square meters and is designed to accommodate up to 1,470 passengers during peak hours.

Design Approach: The project adopts a hybrid approach combining prescriptive and performance-based design in accordance with NFPA 130 standards. This methodology ensures compliance with baseline requirements while enabling optimization for the facility's unique dual function as both a transportation hub and civil defense shelter.

Key Fire Protection Systems: The station …


Fire Protection And Life Safety Analysis Report, Ayoung Yun Jun 2025

Fire Protection And Life Safety Analysis Report, Ayoung Yun

Fire Protection Engineering: Culminating Experience Project Reports

This report evaluates the fire and life safety performance of the proposed building, a two- story, mixed-occupancy facility designed to serve as a civic and cultural hub. The analysis was prepared to assess compliance with the 2021 International Building Code (IBC), NFPA 13, NFPA 72, and related standards, with a particular focus on areas where occupant egress paths challenge prescriptive limitations. The project includes assembly, business, and storage occupancies, and features a large auditorium, classrooms, an exhibition hall, a restaurant, offices, and a double-height atrium. The building is designed as a non-separated mixed-use facility and is classified under Groups A-1, …


Fire Safety Design For Los Angeles County Fire Station 171, Ryan Murrieta Jun 2025

Fire Safety Design For Los Angeles County Fire Station 171, Ryan Murrieta

Fire Protection Engineering: Culminating Experience Project Reports

This report provides a fire safety analysis for Los Angeles County Fire Station 171. To accomplish this, the fire station is analyzed using both a prescriptive and performance-based design approach. With this in mind, the report will show areas where Fire Station 171 is in compliance with codes and standards outlined in the International Building Code (IBC) and the National Fire Protection Agency (NFPA). This report will also recommend improvements for the fire station in areas where the building is not up to current standards and codes.

Fire Station 171 is a two-story Type IIA construction fire station that also …


Ymca Building, Tomas Lins Jun 2025

Ymca Building, Tomas Lins

Fire Protection Engineering: Culminating Experience Project Reports

This project consists of the prescriptive and performance-based analysis of the fire protection and life safety features of the YMCA building in the city of Grants Pass, OR. The building was opened to the public in 1983 and was expanded in 2003. The initial construction is classified as Type IV and is not protected by a sprinkler system. The expanded section has a construction classification of Type II-B and is fully sprinklered. The main occupancies found in the building are Groups A and B. The building includes daycare room classified as Group E. The four core areas of prescriptive analysis …


Srs Training Facility, Brandon Romero Jun 2025

Srs Training Facility, Brandon Romero

Fire Protection Engineering: Culminating Experience Project Reports

This report presents a comprehensive fire protection and life safety analysis of the Savannah River Site (SRS) Training Center. A detailed prescriptive code analysis confirmed the building's compliance with applicable standards regarding construction features, occupancy classification, and fire-rated assemblies. Fire resistance provisions are met, with key areas such as exits, stairwells, and the records storage room. The building’s layout, height, number of stories, and floor area also comply with the allowable limits established by the IBC. Fire protection systems include a proprietary fire alarm system with voice notification, extensive smoke and heat detection coverage, and a wet-pipe sprinkler system designed …


Fire Protection And Life Safety Analysis Report California State University Of Dominguez Hills, Jung Sub Kim Jun 2024

Fire Protection And Life Safety Analysis Report California State University Of Dominguez Hills, Jung Sub Kim

Fire Protection Engineering: Culminating Experience Project Reports

This report provides detailed fire and life safety analysis of the California State University of Dominguez Hills, Innovation and Instruction Building. The building is 4 stories high, accommodating an auditorium, classrooms, labs, and office spaces. Type of construction for the building is II-A. The building will have an aggregate floor area of 83,539 square feet of across four floors.

First half of the report includes prescriptive fire and life safety analysis conducted in accordance with 2021 Edition International Building Code and the applicable Standards, such as National Fire Protection Association (NFPA) 13, Standard for the Installation of Sprinkler Systems, 2022 …


Project Buildings, Anthony Pamintuan Jun 2024

Project Buildings, Anthony Pamintuan

Fire Protection Engineering: Culminating Experience Project Reports

This report analyzes the prescriptive based design of a government-use high-rise building whose primary use is a business office building in California utilizing the California Building Code 2022 Edition. For security purposes, the name of the project will be the “Project Building.” The project site consists of a common podium underground parking garage with two high-rise buildings and an auditorium built on the parking garage. The project buildings that were analyzed consisted of the underground parking garage, the auditorium, and one of the high-rise buildings.

The parking garage is approximately 135,000 square feet consisting of mixed occupancies throughout. The mixed …


Fire & Life Safety Evaluation Of The Goff Health Sciences And Technology Building, Philip Bond Jun 2024

Fire & Life Safety Evaluation Of The Goff Health Sciences And Technology Building, Philip Bond

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this report is to practically apply the information conveyed in the Cal Poly Fire Protection Engineering Master of Science program by selecting a building and analyzing prescriptive and performance-based design features that accomplish the building’s life safety strategy. The selected building is the Goff Health Sciences and Technology Building located in Oak Ridge, Tennessee.

The Goff Health Sciences and Technology Building is a three-story educational facility with business, education, and assembly occupancies. The fire safety strategy of the building depends on a fire alarm communication system, wet pipe sprinkler system, structural fire protection components, and egress elements …


Office Building, Grant Iwamoto Jun 2024

Office Building, Grant Iwamoto

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this report is to conduct a prescriptive and performance-based fire and life safety analysis of a building. The chosen building is a five-story building with a basement and uses construction type IB, primarily with steel framing with concrete fill over metal deck. The use of the building is manufacturing, assembly area, open concept office space, and storage, and the total area is approximately 104,000 square feet.

The prescriptive analysis covers the building and fire code requirements such as allowable height, stories, and area and all the fire protection systems in the building including the fire sprinkler system, …


Training Facility, Andrew Kuharski Jun 2024

Training Facility, Andrew Kuharski

Fire Protection Engineering: Culminating Experience Project Reports

The Training Facility is a two-story, 142,500 sq. ft. building constructed in 1994 at the Savannah River Site DOE complex. The facility primarily contains training rooms, office space, and a cafeteria. Fire protection features of the Training Facility are detailed in this report, including key life safety, suppression, alarm, and structural features. The building has several deficiencies; the second floor has an occupant load of 911 occupants but is only provided with an exit capacity of 800, and occupancy size per floor exceeds what is allowed for assembly occupancies on the first floor. The travel distance from the records storage …


Two-Story Dod Office Building, Jacob Ost Jun 2024

Two-Story Dod Office Building, Jacob Ost

Fire Protection Engineering: Culminating Experience Project Reports

This report is a comprehensive analysis of the fire protection and life safety components for an administrative office building designed for the Department of Defense. The owner of the facility has requested that all identifying information, including name and location, not be included in this report and has since been removed from the documents.

The building was designed in 2019 and is currently under construction. The building is two stories with a total area of approximately 125,000 square feet. The building is primarily used as office space for administrative personnel and consists of open and single-user office space, conference rooms, …


University Of Washington Bill & Melinda Gates Center For Computer Science & Engineering, Devin Ide Jun 2023

University Of Washington Bill & Melinda Gates Center For Computer Science & Engineering, Devin Ide

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this report is to analyze and evaluate the prescriptive and performance-based criteria used to design the fire protection systems installed in the Gates Center for Computer Science and Engineering at the University of Washington, Seattle Campus. The Gates Center is a five-story building housing business and assembly spaces such as classrooms, workrooms, offices, a lecture hall, event center, and a café. The main architectural feature is a central atrium, which connects the ground, first, second, and third floors of the building.

Aspects of the prescriptive-based fire protection design include egress, automatic sprinkler systems, detection and notification devices, …


Fire Protection Analysis Of A K-12 Classroom Building, Raymond Yip Jun 2023

Fire Protection Analysis Of A K-12 Classroom Building, Raymond Yip

Fire Protection Engineering: Culminating Experience Project Reports

The report evaluates the fire protection features of a K-12 classroom building (Bldg. B) in San Bernardino County, California. Bldg. B is a two-story Type V-A light timber frame construction. At the time of this report’s composition, Bldg. B is undergoing modernization construction. The fire protection analysis of this building consists of prescriptive and performance portions.

The prescriptive analysis verifies the compliance of building egress, passive, and active protection features with the 2019 edition of California Codes of Regulations Title 24 (Title 24) and Title 24-adopted National Fire Protection Association (NFPA) standards. The analysis comprises of four sections: egress, structural …


Food Processing And Campus Market (Building 24), Ian De Vries Jun 2023

Food Processing And Campus Market (Building 24), Ian De Vries

Fire Protection Engineering: Culminating Experience Project Reports

This report provides a prescriptive and performance-based analysis of the Food Processing Building located on Cal Poly’s campus in San Luis Obispo, California. Food science and nutrition classes take place at the facility where faculty and students manufacture food products such as chocolates, jams, and barbecue sauces. The finished products are offered for sale in the building’s mercantile area, known as the Campus Market, in addition to other retail locations around the city. The Food Processing Building is considered mixed use with portions of the building classified as moderate-hazard factory (F-1), moderate-hazard storage (S-1), business (B), mercantile (M), and assembly …


Office Building In Moffett Park District, Cody Williams Jun 2023

Office Building In Moffett Park District, Cody Williams

Fire Protection Engineering: Culminating Experience Project Reports

The objective of this review is to analyze and evaluate the fire safety of a 5-story office building located in the Moffett Park District in Sunnyvale, California. The building is constructed largely of mass timber and classified as a Type IIIA building used primarily as office space. The first section of the report focuses on the building’s defining characteristics and use cases. The second portion of the report presents a comprehensive review of egress design, fire alarm systems, fire suppression systems, structural design, implementation of mass timber elements, and flammability requirements. The results of the analysis show that the building …


Fire Protection Analysis Project – 9220 Zanzibar Lane Maple Grove, Mn, Brian Vandal Jun 2022

Fire Protection Analysis Project – 9220 Zanzibar Lane Maple Grove, Mn, Brian Vandal

Fire Protection Engineering: Culminating Experience Project Reports

This report contains an analysis of the life safety and fire protection features of a four-story apartment building in Maple Grove, Minnesota. The report is a part of the final project intended to meet the requirements for the Culminating Experience of the California Polytechnic Master of Science Fire Protection Engineering Program.

The apartment building chosen for the analysis is a mixed-use four-story wood-framed structure. The first floor of this structure includes office space for building management, a meeting space, and various electrical and mechanical spaces as well as apartments. There are exit stairways on each end of the structure extending …


Warren Baker Center For Science And Mathematics- Fire Protection And Life Safety Analysis, Logan Honeycutt Jun 2022

Warren Baker Center For Science And Mathematics- Fire Protection And Life Safety Analysis, Logan Honeycutt

Fire Protection Engineering: Culminating Experience Project Reports

This report covers an analysis of the fire protection features within the Warren Baker Center for Science and Mathematics Building. This document first discusses the prescriptive requirements for the building as determined by applicable code. The items to be discussed, as they relate to prescriptive requirements, include the means of egress and relatable components, fire resistive construction, fire alarm system, fire sprinkler system, and smoke control system. All components were analyzed and compared to each applicable code to assess whether these specific fire protection systems were designed correctly.

In addition to an analysis of the prescriptive measures in this facility, …


La Universal, Jose Emilio Salgado Florencia Jun 2022

La Universal, Jose Emilio Salgado Florencia

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this project was to analyze and compare the existing fire protection systems in “LA UNIVERSAL” building to current applicable codes and standards. Both prescriptive based analysis and performance-based analyses were performed.

The prescriptive based analyses included analyzing the structural fire protection, fire suppression, fire alarm, and egress systems. There are many fire protection features that do not meet the requirements established by the NFPA standards. The fire alarm panel does not provide enough address for the required number of devices required in the building. Emergency lights do not provide the minimum illumination established in NFPA 101. The …


Two-Storey Office Building, Colin Mallett Jun 2022

Two-Storey Office Building, Colin Mallett

Fire Protection Engineering: Culminating Experience Project Reports

This FPE 596 culminating project report was developed to meet the requirements for completion of the Fire Protection Master’s Program at Cal Poly. The report is intended to provide a detailed understanding of fire and building code requirements as well as describe both prescriptive and performance based approaches to human behavior in fire scenarios, building evacuation strategies, egress design and tenability analysis. An overall determination will be made to evaluate if the building provides the expected levels of safety for building occupants from fire.

The office building #211 was designed and constructed to be compliant with the International Building Code …


Mount Sac Gym & Aquatics Center: Fire & Life Safety Report, Alex Hoeft Jun 2022

Mount Sac Gym & Aquatics Center: Fire & Life Safety Report, Alex Hoeft

Fire Protection Engineering: Culminating Experience Project Reports

This report has been prepared to review and analyze the Fire and Life Safety status of the proposed Gym & Aquatics building at Mt. San Antonio College. This was done using two methods: prescriptive and performance based. The prescriptive section examines the explicitly code-mandated requirements for the building and the performance-based section examines implicit requirements for the building based on the goals presented in the Life Safety Code, NFPA 101.

The subject building is a 147,000 square foot, two-story, steel-framed athletics complex occupied primarily for assembly and business uses. The structure has an indoor and outdoor component with two gymnasiums …


Grange Insurance Audubon Center-Fire Protection Life Safety Report, Gabriel Levy Jun 2022

Grange Insurance Audubon Center-Fire Protection Life Safety Report, Gabriel Levy

Fire Protection Engineering: Culminating Experience Project Reports

This technical approach narrative presents the intent and methodology of the Fire Protection and Life Safety systems for the Grange Insurance Audubon Center located at 505 W Whittier St. Columbus OH 43215. The primary goal of the structure is to provide life and property protection in a fire scenario while taking into account the costs of implementing the criterion and risks associated with the facility. This will be achieved through the appropriate application of requirements listed in the 2015 International Building Code (IBC) and the International Fire Code (IFC) as adopted by the City of Columbus, Ohio, and any reference …


Jack E Brown Chemical Engineering Building At Texas A&M University, Daniel Higdon Jun 2022

Jack E Brown Chemical Engineering Building At Texas A&M University, Daniel Higdon

Fire Protection Engineering: Culminating Experience Project Reports

The Jack E Brown Chemical Engineering building at Texas A&M is located in College Station, TX. While this building is dedicated to chemical engineering, it serves many different departments as they use the lecture halls on the first floor. It was built and opened in 2004 and has 206,500 square feet with 7 stories. The building consists of multiple labs as well as study hall rooms, computer labs, offices, and the normal MEP/storage rooms. Jack E Brown building is one of the foremost buildings of the Texas A&M engineering quadrant and is further proof that Texas A&M desires to keep …


Fire Safety Management Plan For South Texas Project Turbine Generator Building, Brett Long Jun 2022

Fire Safety Management Plan For South Texas Project Turbine Generator Building, Brett Long

Fire Protection Engineering: Culminating Experience Project Reports

This report includes a fire protection and life safety analysis of the South Texas Project Turbine Generator Building (TGB). This analysis was done to fulfill the requirement for the Master of Science Degree in Fire Protection Engineering from California Polytechnic State University. The Turbine Generator Building consists of three elevations and is Type II-B construction. The TGB’s primary use is a special-purpose industrial building housing the turbine generator, main feed pumps, condensate pumps, condenser, feed water re-heaters, secondary cold chemistry lab, Balance-of-Plant (BOP) diesel, batteries, and switchgear, 13.8 kVA switchgear, and various other systems and components. This analysis consists of …


Fire Protection And Life Safety Analysis Of Christopher Cohan Center, Kristen Dentici Jun 2022

Fire Protection And Life Safety Analysis Of Christopher Cohan Center, Kristen Dentici

Fire Protection Engineering: Culminating Experience Project Reports

This report analyzes the fire protection and life safety systems of the Christopher Cohan Center. The building was assessed from both a prescriptive and performance-based approach.

The prescriptive design analyzed the code requirements for the building based on the 2018 IBC, with some consideration for the codes in place at the time of construction. The prescriptive analysis main focus was on egress systems, fire alarm and detection, fire suppression, and structural fire protection. The egress analysis found that the exits and exit configuration were sufficient for the occupant loads that were calculated for the building. The fire alarm and detection …


B-91 Fire Protection Analysis, Evan Phillips Jun 2021

B-91 Fire Protection Analysis, Evan Phillips

Fire Protection Engineering: Culminating Experience Project Reports

B-91 is a multiuse building on a Department of Defense installation rented out to a defense contractor consisting of laboratory, office, storage, and utility spaces. To determine the adequacy of the building’s fire protection systems as determined by the state-adopted 2015 International Building Code, a prescriptive analysis was performed with specific areas of focus on the building construction and occupancy, emergency egress capacity, fire suppression systems, and fire alarm systems. The building is compliant with code requirements in its construction and the fire alarm systems are adequately designed to provide notice, but the egress from the building’s main conference room …


College Sports Center Fire Protection Analysis, Elijah Kimmig Jun 2021

College Sports Center Fire Protection Analysis, Elijah Kimmig

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this project was to analyze and compare the existing fire protection systems in the college sports center to current applicable codes and standards. Both prescriptive based analysis and performance based analyses were performed.

The prescriptive based analyses included analyzing the structural fire protection, fire suppression, fire alarm, and egress systems. Overall, the majority of the fire protection systems appeared to meet the requirements of the current codes but there are a few items that were found that appear to not meet current code. These items are listed below along with recommendations to mitigate: (1) Placement of certain …


Fire Protection Analysis Of Johnson Controls Office Building, Derek Driscoll Jun 2021

Fire Protection Analysis Of Johnson Controls Office Building, Derek Driscoll

Fire Protection Engineering: Culminating Experience Project Reports

This project report contains a fire and life safety analysis of the Johnson Controls Office Building. The building is located in Los Angeles, California. The building is a mixed use occupancy with office spaces, meeting rooms, training rooms, and a warehouse for storing fire sprinkler and fire alarm materials. The building is one level with a mezzanine. It is attached to another building and separated by fire barrier so that they are considered separate buildings. This report contains a prescriptive analysis and a performance-based design analysis of the building.

The prescriptive code requirements were determined based on the 2019 edition …


Construction Innovation Center At California Polytechnic State University, James Hunter Gildart Jun 2021

Construction Innovation Center At California Polytechnic State University, James Hunter Gildart

Fire Protection Engineering: Culminating Experience Project Reports

The building of interest for this project is the Construction Innovation Center (CIC) at California Polytechnic State University, San Luis Obispo. The CIC consists of 3 structures (buildings A, B, and C) equipped throughout with a wet pipe automatic sprinkler system and a fire alarm system with smoke detection. This report reviews the prescriptive and performance-based requirements along with providing a fire safety management plan. The prescriptive based portion of this report covers egress, fire alarm, automatic fire sprinklers, flammability, and structural fire protection requirements. Upon completion of the prescriptive code analysis comparing the CIC to the 2015 International Building …


Fire Protection And Life Safety Analysis: Canyon Vista Dining Renovation- University Of California San Diego, Paul Ian Jungco Cabasag Jun 2021

Fire Protection And Life Safety Analysis: Canyon Vista Dining Renovation- University Of California San Diego, Paul Ian Jungco Cabasag

Fire Protection Engineering: Culminating Experience Project Reports

The Canyon Vista Dining project is a renovation of an existing two-story dining facility located in the Warren College area of the University of California San Diego campus for the owners, Housing, Dining and Hospitality. The renovation scope of work comprised a new dining experience with a better diversity of food options and indoor and outdoor seating, which upgraded the first floor, second floor, and mechanical penthouse. In the course of the design and construction, the prescriptive, performance, wildfire, and due diligence design results were utilized during discussions with design team and building permit approval. The project construction was completed …


Christopher Cohan Performing Arts Center Fire Protection And Fire Life Safety Analysis, Alex Dowdy Jun 2021

Christopher Cohan Performing Arts Center Fire Protection And Fire Life Safety Analysis, Alex Dowdy

Fire Protection Engineering: Culminating Experience Project Reports

The Christopher Cohan Performing Arts Center Fire Protection and Life Safety Report evaluates the building’s prescriptive compliance and provides a performance-based analysis. The original construction documents were completed in 1993 in line with UBC 1991 requirements, however, the 2016 Edition of the California Building Code was used for the purpose of this analysis.

The Christopher Cohan Performing Arts Center was constructed as a Type I-B building, fully protected with a sprinkler system and an emergency voice alarm system. The building is located far enough from surrounding buildings as to not require a fire-resistance rated exterior, with the exception of a …