Indoor Air Quality Impacts Of Uncontrolled Air Flow And Depressurization In Eight Commercial Buildings In Central Florida, Florida Solar Energy Center, James Cummings Sep 1995

Indoor Air Quality Impacts Of Uncontrolled Air Flow And Depressurization In Eight Commercial Buildings In Central Florida, Florida Solar Energy Center, James Cummings

FSEC Energy Research Center®

Field investigations were done in 68 commercial buildings to identify uncontrolled air flows and pressure imbalances. Results from eight buildings (six restaurants and two sports facilities) are reported in this paper. Testing included building airtightness tests, identification of building air barrier location, duct system airtightness, characterization of pressure differentials, building air flow balance, and infiltration/ventilation rates. Six restaurants and one sports facility were found to operate at negative pressures which ranged from -0.003 inWC (-0.8 Pa) to -0.173 inWC (-43 Pa) and averaged -0.051 inWC (-12.7 Pa) under normal operation. A second sports facility operates partially at positive pressure and …