Open Access. Powered by Scholars. Published by Universities.®

Education Commons

Open Access. Powered by Scholars. Published by Universities.®

Business

Technological University Dublin

2009

Free Cooling

Articles 1 - 1 of 1

Full-Text Articles in Education

Heat Transfer Correlations For Low Approach Evaporative Cooling Systems In Buildings, Ben Costelloe, Donal Finn Jan 2009

Heat Transfer Correlations For Low Approach Evaporative Cooling Systems In Buildings, Ben Costelloe, Donal Finn

Articles

The experimental performance of an open industrial scale cooling tower, utilising small approach temperature differences (1–3 K), for rejection of heat at the low water temperatures (11–20 °C) typical of chilled ceilings and other sensible air–water heat dissipation systems in buildings, is examined. The study was carried out under temperate maritime climatic conditions (3–18 °C wet-bulb temperature range). Initially a theoretical analysis of the process at typical conditions for this climate was conducted, which indicated that a water to air (L/G) mass flow rate ratio of less than 1.0 was required for effective operation. Consequently for these low L/G ratios, …