Fire Protection Engineering: Culminating Experience Project Reports

Performance-Based Design

Articles 1 - 27 of 27

Full-Text Articles in Other Engineering

Design Fire Robert E. Kennedy Library, California Polytechnic State, San Luis Obispo, Jennifer Ocampo Jun 2023

Design Fire Robert E. Kennedy Library, California Polytechnic State, San Luis Obispo, Jennifer Ocampo

Fire Protection Engineering: Culminating Experience Project Reports

This report evaluates the fire protection system of the Kennedy Building using a prescriptive approach and a performance-based design. The prescriptive approach evaluates code compliance of the structural design, fire suppression system, alarm and detection and smoke control. The performance-based design evaluates egress and life safety protection and three design fires that could potentially compromise the goals and objectives of the design.

The Kennedy Building is on the Campus of Cal Poly, San Luis Obispo and serves as the primary library of the university. This building has five stories of mixed occupancies. It is partially sprinklered, has limited automatic detection …


A Fire Protection And Life Safety Analysis Of An Oupatient Healthcare System Building, Conrad Chandler Jun 2023

A Fire Protection And Life Safety Analysis Of An Oupatient Healthcare System Building, Conrad Chandler

Fire Protection Engineering: Culminating Experience Project Reports

The subject building of the report is an outpatient healthcare system building that is a two stories in height and 184,670 SF building. This building offers primary, specialty, and mental health outpatient care to patients throughout its state of location.

The facility is a mixed occupancy building with business as the primary occupancy, a surgery suite that classifies as an ambulatory health care occupancy, and assembly uses in the conference rooms, kitchen, and canteen. The Authority Having Jurisdiction (AHJ) has adopted the National Fire Codes (NFC) published by the National Fire Protection Association (NFPA), and throughout this report, the life …


Process Support Building Savannah River Site, Victoria Zawacki Jun 2022

Process Support Building Savannah River Site, Victoria Zawacki

Fire Protection Engineering: Culminating Experience Project Reports

A report on the fire and life safety analysis of the Savannah River Site Process Support Building is required in order to receive a Master of Science in Fire Protection Engineering from the California Polytechnic State University, San Luis Obispo. The Process Support Building is a two-story office building that was first occupied in 2013, with a floor area of approximately 10,000 ft2. The building contains mainly personal offices, but also contains conference and turnover rooms, a Computer Simulation Room, an Observation Room, and a lunch area. The analysis includes both prescriptive and performance-based analysis.

The Process Support Building is …


Fire Protection And Life Safety Analysis Of A University Conference Center, Amanda Beck Larkin Jun 2022

Fire Protection And Life Safety Analysis Of A University Conference Center, Amanda Beck Larkin

Fire Protection Engineering: Culminating Experience Project Reports

This project report analyzes various aspects of fire protection and life safety design for a University Conference Center, for both prescriptive and performance-based designs. The University Conference Center is a ten-story, high-rise building comprised of various gathering spaces, ranging from small conference rooms to large assembly spaces with auditorium-style seating. The building has a large two-story podium with basement below, with a smaller floor plate, ten-story tower offset to one side.

In the prescriptive analysis, no deficiencies were noted in the water-based suppression or fire resistance analysis. The building construction type, height, area, number of stories, wall and structural ratings, …


Prescriptive And Performance-Based Analysis Of Colorado Liberal Arts College, Victor Wight Jun 2022

Prescriptive And Performance-Based Analysis Of Colorado Liberal Arts College, Victor Wight

Fire Protection Engineering: Culminating Experience Project Reports

This project consists of a prescriptive and performance-based analysis of an existing two-story college building. The building is located in downtown Colorado Springs, Colorado. Colorado Liberal Arts College is used for general education courses with the focus on creative fields such as dance, graphic design, and art. The building consists of classrooms, offices, an art gallery, dance studio, and a bookstore.

A prescriptive based design was completed using the code requirements laid out in the International Building Code (IBC) 2015 Edition and applicable National Fire Protection Association (NFPA) Codes. The prescriptive based analysis consisted of analyzing life safety and egress, …


Bonderson Engineering Center, Hannah Curry Sep 2021

Bonderson Engineering Center, Hannah Curry

Fire Protection Engineering: Culminating Experience Project Reports

As part of the requirements for receiving a Master of Science in Fire Protection Engineering from California Polytechnic State University at San Luis Obispo, a Fire and Life Safety Analysis of the Bonderson Engineering Projects Center located on the Cal Poly San Luis Obispo campus is performed. The analysis consists of both a prescriptive and a performance-based analysis.

The prescriptive analysis focuses on reviewing the as-built conditions within the Bonderson Engineering Projects Center for compliance with the current edition of applicable codes and standards. The analysis is performed using the 2018 Edition of the International Building Code (IBC) and the …


A Fire Protection Life Safety Analysis Of Multipurpose Building, Dalower Hossain Aug 2021

A Fire Protection Life Safety Analysis Of Multipurpose Building, Dalower Hossain

Fire Protection Engineering: Culminating Experience Project Reports

The following report is a fire and hazard protection analysis of a new building. This new building is a multi-purpose building called MPB locates in Gazipur, Dhaka, Bangladesh. The prescriptive requirements set by the codes and standards used at time of construction of the building have been met. The building has been properly classified with respect to occupancy as S1, Group B and F-1 and construction Type I A Sprinklered. Appropriate designs for interior partitions and exterior wall have been identified. Interior finish requirements have been analyzed for a better understanding of aesthetics guidelines. Based on the sprinkler drawing calculations, …


Fire Protection Analysis For The Tritium Engineering Building, Jack Smeck Jun 2021

Fire Protection Analysis For The Tritium Engineering Building, Jack Smeck

Fire Protection Engineering: Culminating Experience Project Reports

This report analyzed several different aspects of the fire protection and life safety strategy for the Tritium Engineering Building (TEB) at the Savannah River Site in Aiken, SC. The TEB is a single-story, Type IIB building that primarily houses engineering and technical staff. The building is approximately 15,560 ft2 and consists of two large “open areas” enclosed by hard- wall offices. Modular workstations are located in both “open areas” and accommodate the majority of the building occupants. This analysis provided both a prescriptive and a performance-based approach for analyzing fire hazards within the building. The prescriptive- based analysis evaluated the …


Powell Building, David John Devinney Jun 2020

Powell Building, David John Devinney

Fire Protection Engineering: Culminating Experience Project Reports

A detailed study of the fire and life safety systems was performed on the Powell Building located in Oak Ridge, TN. This report consists of both prescriptive and performance-based analysis. The prescriptive based analysis reviews the fire and life safety requirements in accordance with the applicable codes. The prescriptive portion of this report included life safety, fire suppression systems, fire alarm and detection systems, and structural fire protection. The performance-based analysis was used with viable fire scenarios to ensure that occupants could safely egress the building. This was accomplished by comparing the Required Safe Egress Time (RSET) with the Available …


Second Baptist Church, Cypress Campus, David Kalinec Jun 2020

Second Baptist Church, Cypress Campus, David Kalinec

Fire Protection Engineering: Culminating Experience Project Reports

This report was created as part of the Master of Science Fire Protection Engineering degree program at California Polytechnic State University at San Luis Obispo. This project summarized the covered subjects during the course of each quarter of the program. The site chosen for this project is Second Baptist Church, Cypress Campus, located in Cypress, TX. This building was chosen because Churches are mixed use buildings that include assembly occupancies and large occupant loads.

A prescriptive-based code evaluation was performed on the building according to the 2012 editions of the international building code and fire code, adopted at the time …


Culminating Course Progress Report For The Na893 Community Support Center, Yokosuka Naval Base, Japan, Kazuo Miura Jun 2020

Culminating Course Progress Report For The Na893 Community Support Center, Yokosuka Naval Base, Japan, Kazuo Miura

Fire Protection Engineering: Culminating Experience Project Reports

This is the culminating project report for the Fire Project Engineering Master’s of Science at California Polytechnic at San Luis Obispo. This project will consider a project for the US military in Japan, JFY893 Community Support Facility, Yokosuka Naval Base. The subject facility consists of a library, education center, family services, and other community services. The Library shall serve as the Main Base Library, keep and store books and provide library services for active duty population, dependents and retirees. The Education Center provides services for advancing of the academic, technical, and vocational education of military personnel of all grades and …


New Campus Life Center Fire Protection Evaluation, Shawn R. Block Jun 2020

New Campus Life Center Fire Protection Evaluation, Shawn R. Block

Fire Protection Engineering: Culminating Experience Project Reports

This project report is a fire and life safety evaluation of a newly constructed building. The new Campus Life Center (CLC) building is located on the campus of Emory University in Atlanta, Georgia. The CLC is a student center where students, staff, and guests can gather to socialize, study, eat and attend conferences. The prescriptive requirements were based on the Georgia State Fire Codes, adopted on January 2014 and served as code of record for this facility. Occupant classification was established from both International Building Code (IBC) and Life Safety Code (LSC), NFPA 101, to determine construction type, interior finish …


Cal Poly State University Robert E. Kennedy Library Fire Protection Analysis Report, Timothy Anderson Jun 2019

Cal Poly State University Robert E. Kennedy Library Fire Protection Analysis Report, Timothy Anderson

Fire Protection Engineering: Culminating Experience Project Reports

This report determines whether or not the fire protection and life safety features of Robert E. Kennedy Library are consistent with the fire protection objectives established in nationally recognized fire protection codes and standards. This analysis is performed to establish a technical baseline for identification of fire protection deficiencies.

Kennedy Library is the campus student library at California Polytechnic State University. The facility provides resources and services in a variety of media to meet the needs of university students and faculty.

This analysis consists of a prescriptive analysis and a performance-based analysis. The prescriptive analysis is an analysis of the …


A Fire Protection Life Safety Analysis Of Permian Oil Plaza, Nick Francis Mar 2019

A Fire Protection Life Safety Analysis Of Permian Oil Plaza, Nick Francis

Fire Protection Engineering: Culminating Experience Project Reports

The Permian Oil Plaza (POP) is a four story building located in Midland, TX. This facility was designed to provide over 200,000 square feet of office space to approximately 500 employees. The building was constructed of unprotected non-combustible (Type II-B) building materials and was completed in late 2015. An assessment of the building’s fire and life safety systems was performed to ensure these systems were designed and installed in a manner that meets, or exceeds, the intent of pertinent building codes and fire safety standards. This assessment included a prescriptive based analysis, as well as a performance-based analysis. The prescriptive …


Prescriptive And Performance Analysis Of Cold Machine Shop, John Kline Jun 2018

Prescriptive And Performance Analysis Of Cold Machine Shop, John Kline

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this report is to analyze the fire and life safety aspects of the Cold Machine Shop located on the central coast of California. This report includes both a prescriptive and performance based analysis.

The prescriptive analysis will evaluate the building as follows, to ensure compliance with standard codes: 1)Egress analysis and design using NFPA 101, "Life Safety Code", 2)Fire detection, alarms, and communication systems using NFPA 72, "National Fire Alarm and Signaling Code", 3)Water-based fire suppression systems using NFPA 13, " Standard for Installation of Sprinkler Systems" and NFPA 14, " Standard for the Installation of Standpipe …


University Student Services Center, Ivan Orlando Mendoza Jun 2018

University Student Services Center, Ivan Orlando Mendoza

Fire Protection Engineering: Culminating Experience Project Reports

The building was found to be generally compliant with the requirements set forth in the codes and standards, any discrepancies are addressed within the report in their respective sections. The prescriptive-based analysis was performed using the appropriate NFPA standards, the Life Safety Code (LSC) and the International Building Code (IBC).

The building is three storied and has an overall gross floor area of 101,579 sq ft. It is classified as a mixed occupancy use with a calculated total occupant load of 2,866 occupants and is being evaluated as a Type II-B structure as defined in the IBC. It is protected …


Sandia National Laboratories' Building 858/North Fabrication Facility, Daniel Garcia Dec 2017

Sandia National Laboratories' Building 858/North Fabrication Facility, Daniel Garcia

Fire Protection Engineering: Culminating Experience Project Reports

In this report, a fire protection and fire hazard analysis has been performed on a semi- conductor facility, abbreviated as the Fab, located on Kirtland Air Force Base in Albuquerque, New Mexico. The Fab is part of the MESA complex which is operated by the NTESS Corporation for the Department of Energy (DOE) at Sandia National Laboratories. The prescriptive analysis of this report addresses the various fire protection systems in the facility such as fire suppression, and fire alarm. The prescriptive analysis is based on national codes and standards from the National Fire Protection Association (NFPA) and from the International …


Los Angeles Air Force Base Fitness Center, Colin White Jun 2017

Los Angeles Air Force Base Fitness Center, Colin White

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this report is to evaluate the life safety features of the Los Angeles Air Force Base Fitness Center, located on Los Angeles Air Force Base in El Segundo, California. This report is produced in partial fulfillment of the requirements of a Master’s of Science in Fire Protection Engineering from the Fire Protection Engineering Program at California Polytechnic State University’s San Luis Obispo Campus. This analysis approaches life safety in the fitness center from two angles. First, a prescriptive approach is used to evaluate the building’s compliance with current codes and standards that govern construction and maintenance of …


Child Development Center- Fire Protection Analysis, Tyler Ball Jun 2017

Child Development Center- Fire Protection Analysis, Tyler Ball

Fire Protection Engineering: Culminating Experience Project Reports

This report contains two separate forms of analysis, Prescriptive-Based Analysis and Performance-Base Analysis. The Prescriptive Analysis discusses an overview of the building and its features whereas the Performance-Based Analysis discusses the building meeting applicable codes and standards as discussed in NFPA 101 Life Safety Code 2012 Edition, Unified Facilities Code (UFC), International Building Code (IBC) 2012 Edition, and the SFPE Handbook of Fire Protection Engineering. The Child Development Center (CDC) was analyzed as a new construction building. There are also noted assumptions within the report where necessary information about the building could not be obtained due to information restrictions from …


Maumus Center- Fire Protection Engineering Analysis, Tyler Mobley Jun 2017

Maumus Center- Fire Protection Engineering Analysis, Tyler Mobley

Fire Protection Engineering: Culminating Experience Project Reports

This report is a fire protection engineering analysis of the Maumus Center, a science center and planetarium, in Arabi, Louisiana. The objective of this analysis is to outline the code defined requirements and to confirm the minimum level of safety from fire is attained. Analyzed in the report are the design requirements prescribed in the adopted building and life safety codes, and the performance of the prescribed design. The prescriptive review addresses the building construction in regards to fire protection, the means of egress, the water‐based fire suppression system, and the fire alarm system. The performance review incorporates the goals …


Office Building- Fire Protection Systems Evaluation, Christine Newton Jun 2016

Office Building- Fire Protection Systems Evaluation, Christine Newton

Fire Protection Engineering: Culminating Experience Project Reports

This report is a Life Safety Code (LSC) and fire protection systems evaluation of an office building located in Colorado. This report covers the prescriptive analysis of the building, as well as the performance‐based aspect of the evaluation.

The prescriptive analysis of this report includes assessment of the building code for structural design, means of egress, detection and notification systems, smoke control system, and the water‐ based fire suppression system for this building. The 2012 International Building Code (IBC) and the National Fire Protection Agency (NFPA) 101 LSC were used for the prescriptive based evaluation and the building was determined …


Orange Grove Library- Prescriptive And Performance-Based Fire And Life Safety Evaluation, David A. Boackle Jun 2016

Orange Grove Library- Prescriptive And Performance-Based Fire And Life Safety Evaluation, David A. Boackle

Fire Protection Engineering: Culminating Experience Project Reports

This report describes the analysis of the Orange Grove Library in Gulfport, Mississippi, using prescriptive and performance-based techniques to evaluate fire and life safety. The prescriptive analysis is broken down into four components: alarm, egress, structural and suppression. Prescriptive codes are written by consensus, such that adhering to these codes will produce a reasonable balance between cost, function and safety. The performance-based design analysis uses analytical tools to predict how this particular building would perform under specific fire conditions, chosen based on the actual building in place. Life safety is the primary goal of this analysis. Achievement of this goal …


Mayo Clinic Specialties Building- Fire And Life Safety Report, Taylor Bateman Jun 2016

Mayo Clinic Specialties Building- Fire And Life Safety Report, Taylor Bateman

Fire Protection Engineering: Culminating Experience Project Reports

The MCS Building is a medical clinic facility located in Phoenix, Arizona. It is a four-story building with roughly 40,000 square feet of occupied floor area per story. The MCS Building is connected to an adjoining hospital on all four occupied stories, and is not considered a separate building from the hospital in accordance with the 2012 International Building Code (IBC). However, for the academic purposes of this report, only the fire and life safety features of the MCS Building are discussed, as if it is a separate building. It consists primarily of medical offices and outpatient clinics, and is …


Fire Protection Engineering Analysis For Building 910 - Sandia National Labs/Ca, Mo Mosallaei Jun 2015

Fire Protection Engineering Analysis For Building 910 - Sandia National Labs/Ca, Mo Mosallaei

Fire Protection Engineering: Culminating Experience Project Reports

This Fire Protection Engineering analysis was performed on Building 910 in Sandia National Laboratories in Livermore, CA to examine the building’s fire safety and fire protection criteria which originally adhered to the 1985 Uniform Building Code. The object of this analysis is to determine the degree of compliance with the prescriptive codes in place today as well compliance with performance based analysis. For the prescriptive analysis consisted of evaluating the buildings occupancy classification, type of construction, egress design, fire detection and alarm systems, fire sprinkler system, Halon System, and structural fire protection are evaluated in terms of the life safety …


Laboratory Building- Sandia National Laboratories, Albuquerque, Nm, Joshua Herrera Mar 2015

Laboratory Building- Sandia National Laboratories, Albuquerque, Nm, Joshua Herrera

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of the culminating report was to perform a prescriptive-based and performance-based analysis on the fire and life safety systems in the laboratory building at Sandia National Laboratories (SNL). The prescriptive-based analysis determined if the laboratory building met applicable code requirements for life safety systems. The performance-based analysis conducted a series of fire scenarios to ensure the fire and life safety systems provided adequate egress time for occupants in the event of a fire. The prescriptive-based analysis was based on the Life Safety Code (LSC) and International Building Code (IBC). The laboratory building is a mixed occupancy building. The …


Fire And Life Safety Analysis Of The Bonderson Engineering Projects Center, Brian Sackett Jun 2014

Fire And Life Safety Analysis Of The Bonderson Engineering Projects Center, Brian Sackett

Fire Protection Engineering: Culminating Experience Project Reports

As part of the requirements for the Degree of Masters of Science in Fire Protection Engineering from California Polytechnic State University, San Luis Obispo, a prescriptive and performance based design analysis was conducted for the Bonderson Engineering Projects Center building (Cal Poly campus). The purpose of this analysis was to review the Bonderson Engineering Projects Center’s compliance with applicable and recognized fire and building codes with regards to its fire protection systems and features. The fire protection systems and features analyzed in this report include: 1) Egress Systems, 2) Structural Fire Protection, 3) Fire Detection and Alarm Systems, 4) Fire …


Design Analysis Of An Air Force Fuel Cell Maintenance Hangar, Andrew Carmean Jun 2014

Design Analysis Of An Air Force Fuel Cell Maintenance Hangar, Andrew Carmean

Fire Protection Engineering: Culminating Experience Project Reports

A Fuel Cell Maintenance Hangar (FCMH) was constructed in 2013 based on a 2012 design; Figure 1.1.1 is a rendering shown below. This report evaluates the design for life safety, and property protection systems. The facility was designed based on Air Force standard prescriptive methods; the resultant design is compared to minimum prescriptive methods and to as-built drawings. In addition, the property protection design criteria were evaluated by simulating the maximum expected design fire in a hangar bay 1 using Fire Dynamics Simulator (FDS). Section 1 consists of a general overview of the FCMH including descriptions of the facility and …