Articles 1 - 19 of 19

Full-Text Articles in Other Engineering

Fire Analysis Of The Walter F. Dexter Building- Cal Poly, San Luis Obispo, Jeff Jenkins Jun 2014

Fire Analysis Of The Walter F. Dexter Building- Cal Poly, San Luis Obispo, Jeff Jenkins

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this report is to provide a fire analysis of the Walter F. Dexter Building on the California Polytechnic State University, San Luis Obispo Campus. The report will detail egress analysis, notification systems, and building construction in a prescriptive approach. The report will also include a performance based analysis of the building with a designed fire scenario. This performance based analysis will show that in one of the most likely fire scenarios for the building, there is still ample time for the occupants to escape safely.


Construction Warehouse, Ben Johnson Jun 2014

Construction Warehouse, Ben Johnson

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this report is to provide a comprehensive evaluation of the fire protection and life safety design of a warehouse building that serves a large construction project. The results and conclusions from this evaluation are documented herein and supported by analysis when necessary. The gross floor area per story of the construction warehouse is 39,000 ft2. This building is used as a warehousing facility in support of a large construction project. Rack storage of Group A plastics is permitted in this facility to a height of 20 ft. beneath a 24 ft. ceiling on the main floor. Shelf …


Fire Protection Analysis Robert And Margrit Modavi Center For The Performing Arts- Uc Davis, Jeffrey Paterson Jun 2014

Fire Protection Analysis Robert And Margrit Modavi Center For The Performing Arts- Uc Davis, Jeffrey Paterson

Fire Protection Engineering: Culminating Experience Project Reports

This document is the report of the culminating experience as part of the master’s program in fire protection engineering at the California Polytechnic State University, San Luis Obispo. This report contains a life safety analysis of the fire protection systems of a chosen project building. The building examined is the Robert and Margrit Mondavi Center for the Performing Arts, located on the University of California Davis campus. The building was constructed in 2002 where the first performance occurred in October 2002. A large portion of the report applies prescriptive code requirements to evaluate compliance with current codes and standards. The …


Fire And Life Safety Analysis Of The Bonderson Engineering Projects Center, Brian Sackett Jun 2014

Fire And Life Safety Analysis Of The Bonderson Engineering Projects Center, Brian Sackett

Fire Protection Engineering: Culminating Experience Project Reports

As part of the requirements for the Degree of Masters of Science in Fire Protection Engineering from California Polytechnic State University, San Luis Obispo, a prescriptive and performance based design analysis was conducted for the Bonderson Engineering Projects Center building (Cal Poly campus). The purpose of this analysis was to review the Bonderson Engineering Projects Center’s compliance with applicable and recognized fire and building codes with regards to its fire protection systems and features. The fire protection systems and features analyzed in this report include: 1) Egress Systems, 2) Structural Fire Protection, 3) Fire Detection and Alarm Systems, 4) Fire …


Design Analysis Of An Air Force Fuel Cell Maintenance Hangar, Andrew Carmean Jun 2014

Design Analysis Of An Air Force Fuel Cell Maintenance Hangar, Andrew Carmean

Fire Protection Engineering: Culminating Experience Project Reports

A Fuel Cell Maintenance Hangar (FCMH) was constructed in 2013 based on a 2012 design; Figure 1.1.1 is a rendering shown below. This report evaluates the design for life safety, and property protection systems. The facility was designed based on Air Force standard prescriptive methods; the resultant design is compared to minimum prescriptive methods and to as-built drawings. In addition, the property protection design criteria were evaluated by simulating the maximum expected design fire in a hangar bay 1 using Fire Dynamics Simulator (FDS). Section 1 consists of a general overview of the FCMH including descriptions of the facility and …


Hotel- Georgia, Rock Toler Jun 2014

Hotel- Georgia, Rock Toler

Fire Protection Engineering: Culminating Experience Project Reports

The State of Georgia modifies the International Building Code through State amendments, to require a fire resistance rating between residential occupancies and all other occupancies. This fire and life safety analysis report will substantiate the necessity for the barrier in a mixed-use hotel occupancy. The first-half of the report addresses the prescriptive-based code requirements, reporting a compliant design was presented. Then the performance portions primary objective was established, maintain a tenable environment for egressing guest room occupants. Three conditions were evaluated to define a tenable environment, carbon monoxide levels, temperature, and visibility limits. Selecting the location of the fire required …


Fire Protection And Life Safety Evaluation- Houston Community College- San Jacinto Building, Will Clay Jun 2014

Fire Protection And Life Safety Evaluation- Houston Community College- San Jacinto Building, Will Clay

Fire Protection Engineering: Culminating Experience Project Reports

This report evaluates the life safety features of the HCC San Jacinto Building (SJB) both prescriptively and on a performance basis. The goal is to present the building code requirements for the HCC San Jacinto building and determine if the design is in compliance, as well as analyze the building on the basis of performance criteria to determine if there are any excessive threats to life safety. The building is designed in compliance with the Houston Building Code, and takes advantage of lesser requirements for existing features. The performance section determines that based on fire and egress modeling, that while …


Fire And Life Safety Report- Agricultural Sciences Building- Cal Poly, Jonathan Schram Jun 2014

Fire And Life Safety Report- Agricultural Sciences Building- Cal Poly, Jonathan Schram

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this fire and life safety analysis is to provide a conclusion on whether the Agricultural Sciences Building (ASB) meets fire safety goals. The primary fire safety goal is to provide building occupants a safe environment during fire conditions. This goal can be achieved by protecting the occupants not intimate with the initial fire development and improving survivability of those occupants intimate with the initial fire development. A prescriptive-based design approach and a performance-based design approach are used to evaluate building safety. The prescriptive-based approach is used to evaluate the building's structural fire protection systems, fire detection and …


Fire And Life Safety Analysis- Uw Medicine Lake Union Phase 3.1, Marge Hong Jun 2014

Fire And Life Safety Analysis- Uw Medicine Lake Union Phase 3.1, Marge Hong

Fire Protection Engineering: Culminating Experience Project Reports

This report provides a summary of the fire protection and life safety features for UW Medicine Lake Union, a research and laboratory building, in accordance with Seattle Building Code (SBC), International Building Code (IBC), and Life Safety Code (NFPA 101). The objective of this report is to identify if UW Medicine Lake Union meets both the prescriptive and performance based code. The primary fire safety goal is to provide life safety system that reduced the risk of fire-related injuries and loss of life due to fire. The prescriptive analysis is used to identify the building integrity per code. This evaluates …


Fire And Life Safety Analysis- Af Child Development Center, Judy Biddle Jun 2014

Fire And Life Safety Analysis- Af Child Development Center, Judy Biddle

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this fire and life safety report is to determine whether The Air Force (AF) Child Development Center (CDC) Standard Design meets fire safety goals based on an increased child-to staff ratio and provide a prescriptive based analysis of the of the existing codes that the building was constructed under. The primary fire safety goal is to provide building occupants with an environment that is reasonably safe from fire. A prescriptive-based design approach and a performance-based design approach are used to evaluate building safety in regards to occupant protection, structural integrity, and systems effectiveness. The prescriptive-based approach is …


Westside Christian High School, Michael Stewart Jun 2014

Westside Christian High School, Michael Stewart

Fire Protection Engineering: Culminating Experience Project Reports

The building I have chosen to use as the model for exemplifying the components of a wet fire suppression system is Westside Christian High School (WCHS). This building completed construction in January of 2014 and is located at: 8200 SW Pfaffle Street Tigard, Oregon 97223. The existing structure was previously owned and occupied by City Bible Church who will now lease space from the High school during and after construction. The renovations include the addition of space for music, art classes, fitness center, gym, science labs, and others. The renovations will also be widening existing rooms and hallways. The core …


Fire And Life Safety Analysis Of The Grant M. Brown Engineering Building- Cal Poly, Daniel Gregory Blanchat Jun 2014

Fire And Life Safety Analysis Of The Grant M. Brown Engineering Building- Cal Poly, Daniel Gregory Blanchat

Fire Protection Engineering: Culminating Experience Project Reports

This fire and life safety analysis was performed on the Grant M. Brown Engineering Building in order to determine if the building meets the life safety goals set forth by a prescriptive and performance based analysis. This building was built to a strict set of codes and standards. For the prescriptive analysis the buildings egress design, fire detection and alarm systems, fire sprinkler system, occupancy classification, construction type, and structural fire protection are evaluated in terms of the life safety of the occupants. In the performance based design analysis four computer based programs were used to model egress and fire …


Fire And Life Safety Analysis- Cal Poly Recreation Center, Connor Mcgill Jun 2014

Fire And Life Safety Analysis- Cal Poly Recreation Center, Connor Mcgill

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this fire and life safety analysis is to determine whether Cal Poly’s Recreation Center meets fire safety goals. The primary fire safety goal is to provide building occupants with an environment that is tenable and allows for safe egress in the event of a fire, and reduce the likelihood of any catastrophic fire event. This goal can be achieved by protecting the occupants not intimate with the initial fire development and improving survivability of those occupants intimate with the initial fire development, NFPA 101, 2012. A prescriptive-based design approach and a performance-based design approach are used to …


Fire Protection And Life Safety Analysis- Dell Medical School Academic Building, David Gramlich Jun 2014

Fire Protection And Life Safety Analysis- Dell Medical School Academic Building, David Gramlich

Fire Protection Engineering: Culminating Experience Project Reports

This report is on the Dell Medical School Academic Building located in Austin, Texas. The life safety and prescriptive based code requirements are summarized within this report. It also includes conceptual fire protection and fire alarm system design. This report mentions University of Texas System Owner’s Design Guidelines that exceed the required code requirements. This report was developed when the building was in the Design Development stage. Since, code deficiencies have been addressed, and changes have been made to the building during the remainder of the design process, this report does not reflect the actual construction or protection strategies used …


Comprehensive Fire And Life Safety Analysis- Moa Public Works Building- Anchorage, Alaska, Andrew J. Bigalke Jun 2014

Comprehensive Fire And Life Safety Analysis- Moa Public Works Building- Anchorage, Alaska, Andrew J. Bigalke

Fire Protection Engineering: Culminating Experience Project Reports

This report is a Comprehensive Fire and Life Safety Analysis addressing both prescriptive and performance based engineering analysis of the MOA Public Works building located in the Municipality of Anchorage, Alaska. The Public Works building was originally built in 1997 under the code requirements of the Uniform Building Code, as a Type II-N building. An addition was constructed in 2002 using the International Building Code (IBC), 2000 Edition. A prescriptive analysis is performed using the requisite building code and standards currently adopted by the State of Alaska, and by the Municipality of Anchorage. The currently adopted building codes and standards …


Fire Protection And Life Safety Evaluation- Hinesville Cboc Va Clinic, Jeff Dew Jun 2014

Fire Protection And Life Safety Evaluation- Hinesville Cboc Va Clinic, Jeff Dew

Fire Protection Engineering: Culminating Experience Project Reports

The Hinesville MOB will be analyzed throughout the course of this report to determine if it meets the prescriptive-based requirements set forth by local and national regulating bodies. Further, a performance-based approach will be taken to assess the buildings ability to sustain life while a safe and timely evacuation occurs. It will be determined that the Hinesville MOB does comply with all regulations set forth for fire and life safety. In some cases its construction and systems may exceed the required minimum standards. It will contain 100% coverage with an automatic sprinkler system, be equipped with adequate emergency notification system, …


Cal Poly Student Recreation Center Fire Protection Review, Alain N. Mamada Jun 2014

Cal Poly Student Recreation Center Fire Protection Review, Alain N. Mamada

Fire Protection Engineering: Culminating Experience Project Reports

This report summarizes the analysis of the existing fire protection features and systems installed in the Recreation Center building on the Cal Poly campus. The analysis is conducted into two different approaches. A prescriptive analysis approach will examine installed fire protection features and systems in accordance with the International Building Code. The analysis will consider the building as existing building as per IBC provisions. A performance-based approach will assess whether the building occupants will egress the building before conditions become untenable. Fire dynamic simulations will be used to determine the available safe egress time and evacuation simulations will performed to …


Orangeburg Assembly Hall Of Jehovah's Witnesses- Fire Protection And Life Safety Design Analysis, Justin B. Biller Mar 2014

Orangeburg Assembly Hall Of Jehovah's Witnesses- Fire Protection And Life Safety Design Analysis, Justin B. Biller

Fire Protection Engineering: Culminating Experience Project Reports

In partial fulfillment of the requirements for the Degree of Masters of Science in Fire Protection Engineering, a prescriptive and performance-based engineering analysis was performed on the Orangeburg Assembly Hall of Jehovah’s Witnesses. The building was recently constructed and completed in 2013 in Orangeburg, South Carolina to serve as a center for education of Jehovah’s Witnesses on Biblical principles for daily life. More than 300 congregations throughout Georgia and the Carolinas will use the Assembly Hall for their semi-annual assemblies and conventions, with an estimated annual attendance of 190,000 per year. Prescriptive analyses were conducted based primarily upon the provisions …


Fire Protection Life Safety Analysis- Bachelor Enlisted Quarters, Kyle C. Leadon Mar 2014

Fire Protection Life Safety Analysis- Bachelor Enlisted Quarters, Kyle C. Leadon

Fire Protection Engineering: Culminating Experience Project Reports

This Bachelor Enlisted Quarters (BEQ) shall be constructed, arranged, equipped, maintained, and operated in accordance with this report and applicable criteria to ensure a minimum level of life safety and property protection is provided from actual and potential fire hazards. The goal is to ensure the occupants are provided with an environment that is reasonably safe from fire. We accomplish this goal by protecting occupants not intimate with the initial fire development, and by improving the survivability of occupants intimate with the initial fire development. The protection described in this report takes on many forms, from active protection, such as …