Portable Hepa Filtration Successfully Augments Natural-Ventilation-Mediated Airborne Particle Clearance In A Legacy Design Hospital Ward, Mehael Fennelly, S. Hellebust, J. Wenger, D. O'Connor, G.W. Griffith, B.J. Plant, A.P.C. Microbiome Institute
Portable Hepa Filtration Successfully Augments Natural-Ventilation-Mediated Airborne Particle Clearance In A Legacy Design Hospital Ward, Mehael Fennelly, S. Hellebust, J. Wenger, D. O'Connor, G.W. Griffith, B.J. Plant, A.P.C. Microbiome Institute
Articles
As the severe acute respiratory syndrome coronavirus-2 pandemic has proceeded, ventilation has been recognized increasingly as an important tool in infection control. Many hospitals in Ireland and the UK do not have mechanical ventilation and depend on natural ventilation. The effectiveness of natural ventilation varies with atmospheric conditions and building design. In a challenge test of a legacy design ward, this study showed that portable air filtration significantly increased the clearance of pollutant aerosols of respirable size compared with natural ventilation, and reduced spatial variation in particle persistence. A combination of natural ventilation and portable air filtration is significantly more …