Open Access. Powered by Scholars. Published by Universities.®
Articles 1 - 1 of 1
Full-Text Articles in Engineering
Insulation Condition Assessment Of Power Transformers Using Accelerated Ageing Tests, Mohammad Mirzaie, Ahmad Gholami, Hamid Reza Tayebi
Insulation Condition Assessment Of Power Transformers Using Accelerated Ageing Tests, Mohammad Mirzaie, Ahmad Gholami, Hamid Reza Tayebi
Turkish Journal of Electrical Engineering and Computer Sciences
Thermal stress due to losses and environment temperature causes degradation to paper/oil insulation systems in transformers, even at operating temperature. Experience indicates that thermal ageing of oil and paper in power transformers leads to the change of some insulation characteristics. In this paper, insulating papers immersed in oil have been acceleratory aged at 140, 150, and 160 °C under laboratory conditions. Some of the oil properties, such as water content, breakdown voltage, acidity, together with the aged insulating paper properties such as electric strength, dielectric dissipation factor and tensile strength were measured and analyzed. Also, insulation system conditions under thermal …