Controlling Ventilation And Space Depressurization Inrestaurants Inhot And Humid Climates, Florida Solar Energy Center, Charles Withers, Jr. Sep 1997

Controlling Ventilation And Space Depressurization Inrestaurants Inhot And Humid Climates, Florida Solar Energy Center, Charles Withers, Jr.

FSEC Energy Research Center®

Testing was performed in 9 restaurants to identify uncontrolled air flows and pressure imbalances, building and duct system airtightness, building air barrier location, pressure differentials, building air flow balance, and ventilation rates. All restaurants are depressurized under normal operating conditions, ranging from -1.0 to -43 pascals. Space depressurization is a function of exhaust fan flow rates, missing or undersized make-up air, intermittent outdoor air caused by the cycling of air handlers, dirty outdoor air and make-up air filters, and building airtightness. Ventilation rates were found to be high, generally exceeding ASHRAE 62-1989 minimum recommended levels. Pressure imbalances and excessive ventilation …