Impacts Of Duct Leakage On Infiltration Rates, Space Conditioning Energy Use, And Peak Electrical Demand In Florida Homes, Florida Solar Energy Center, James Cummings Jan 1991

Impacts Of Duct Leakage On Infiltration Rates, Space Conditioning Energy Use, And Peak Electrical Demand In Florida Homes, Florida Solar Energy Center, James Cummings

FSEC Energy Research Center®

Testing for duct leakage was done in 91 homes. Tracer gas tests found that infiltration rates were four times greater when the air handler was operating than when it was off. Return leaks were found to average 10.0% of air handler total flow. House airtightness, in 63 of these homes, determined by blower door testing, averaged 12.38 air changes per hour at 50 Pascals (ACH50). When the duct registers were sealed, ACH50 decreased to 10.93, indicating that 11.7% of the house leaks were in the duct system.

Duct repairs were made on 25 homes. Blower door tests found 12.30 air …