Fire Protection Analysis Of A K-12 Classroom Building, Raymond Yip Jun 2023

Fire Protection Analysis Of A K-12 Classroom Building, Raymond Yip

Fire Protection Engineering: Culminating Experience Project Reports

The report evaluates the fire protection features of a K-12 classroom building (Bldg. B) in San Bernardino County, California. Bldg. B is a two-story Type V-A light timber frame construction. At the time of this report’s composition, Bldg. B is undergoing modernization construction. The fire protection analysis of this building consists of prescriptive and performance portions.

The prescriptive analysis verifies the compliance of building egress, passive, and active protection features with the 2019 edition of California Codes of Regulations Title 24 (Title 24) and Title 24-adopted National Fire Protection Association (NFPA) standards. The analysis comprises of four sections: egress, structural …


The Acme Building Fire Hazards Analysis, Russ Livesay Jun 2023

The Acme Building Fire Hazards Analysis, Russ Livesay

Fire Protection Engineering: Culminating Experience Project Reports

This Fire Hazards Analysis (FHA) was written using modern fire protection engineering principles to characterize the Applied Chemistry Management and Enrichment (ACME) Building at the Pacific Northwest National Research Area (PNNRA) using both a prescriptive-based and performance-based analysis to ensure the building and occupants can be safe in fire conditions. Recommendations are made as part of this analysis to improve the survivability of this structure if a fire were to occur.

This building was found to be compliant with the prescriptive code requirements from the 2018 International Building Code except for a few minor issues that are currently being repaired. …


8 Observatory Road- Fire Protection & Life Safety Analysis, Jeffrey Chiu Jun 2022

8 Observatory Road- Fire Protection & Life Safety Analysis, Jeffrey Chiu

Fire Protection Engineering: Culminating Experience Project Reports

A fire protection and life safety analysis was performed on the building “8 Observatory Road” located in Tsim Sha Tsui, Hong Kong. This analysis was performed as part of the fulfillment of requirements for Master of Science in Fire Protection Engineering degree from California Polytechnic State University, San Luis Obispo.

This report covers both a prescriptive and performance-based analysis. This building was designed and constructed in Hong Kong, adhering to the local codes and British Standard. For this report, the building was analyzed to the requirements of the International Building Code (IBC) and National Fire Protection Association (NFPA) Standards. For …


Jack E Brown Chemical Engineering Building At Texas A&M University, Daniel Higdon Jun 2022

Jack E Brown Chemical Engineering Building At Texas A&M University, Daniel Higdon

Fire Protection Engineering: Culminating Experience Project Reports

The Jack E Brown Chemical Engineering building at Texas A&M is located in College Station, TX. While this building is dedicated to chemical engineering, it serves many different departments as they use the lecture halls on the first floor. It was built and opened in 2004 and has 206,500 square feet with 7 stories. The building consists of multiple labs as well as study hall rooms, computer labs, offices, and the normal MEP/storage rooms. Jack E Brown building is one of the foremost buildings of the Texas A&M engineering quadrant and is further proof that Texas A&M desires to keep …


La Universal, Jose Emilio Salgado Florencia Jun 2022

La Universal, Jose Emilio Salgado Florencia

Fire Protection Engineering: Culminating Experience Project Reports

The purpose of this project was to analyze and compare the existing fire protection systems in “LA UNIVERSAL” building to current applicable codes and standards. Both prescriptive based analysis and performance-based analyses were performed.

The prescriptive based analyses included analyzing the structural fire protection, fire suppression, fire alarm, and egress systems. There are many fire protection features that do not meet the requirements established by the NFPA standards. The fire alarm panel does not provide enough address for the required number of devices required in the building. Emergency lights do not provide the minimum illumination established in NFPA 101. The …


Fire Protection System Analysis Of Air National Guard Readiness Center, Steven A. Waidelich Sep 2021

Fire Protection System Analysis Of Air National Guard Readiness Center, Steven A. Waidelich

Fire Protection Engineering: Culminating Experience Project Reports

This report analyzes the impact of a fire located in the atrium at the Air National Guard Readiness Center (ANGRC) located at Joint Base Andrews, Maryland. The fifth floor is an enclosed penthouse used to enclose mechanical and electrical equipment. International Building Code (IBC) 2006 and 2005, section 506.1, excludes elevator penthouses of this type from the height and area calculations. The four occupied floors are used for office areas with the three- story atrium opening onto the balcony of the second- and the third-floor office area, and the second-floor conference center.

The prescriptive portion of this analysis looked at …


Bonderson Engineering Center, Hannah Curry Sep 2021

Bonderson Engineering Center, Hannah Curry

Fire Protection Engineering: Culminating Experience Project Reports

As part of the requirements for receiving a Master of Science in Fire Protection Engineering from California Polytechnic State University at San Luis Obispo, a Fire and Life Safety Analysis of the Bonderson Engineering Projects Center located on the Cal Poly San Luis Obispo campus is performed. The analysis consists of both a prescriptive and a performance-based analysis.

The prescriptive analysis focuses on reviewing the as-built conditions within the Bonderson Engineering Projects Center for compliance with the current edition of applicable codes and standards. The analysis is performed using the 2018 Edition of the International Building Code (IBC) and the …


Construction Innovation Center At California Polytechnic State University, James Hunter Gildart Jun 2021

Construction Innovation Center At California Polytechnic State University, James Hunter Gildart

Fire Protection Engineering: Culminating Experience Project Reports

The building of interest for this project is the Construction Innovation Center (CIC) at California Polytechnic State University, San Luis Obispo. The CIC consists of 3 structures (buildings A, B, and C) equipped throughout with a wet pipe automatic sprinkler system and a fire alarm system with smoke detection. This report reviews the prescriptive and performance-based requirements along with providing a fire safety management plan. The prescriptive based portion of this report covers egress, fire alarm, automatic fire sprinklers, flammability, and structural fire protection requirements. Upon completion of the prescriptive code analysis comparing the CIC to the 2015 International Building …


Fire Protection Analysis Of Johnson Controls Office Building, Derek Driscoll Jun 2021

Fire Protection Analysis Of Johnson Controls Office Building, Derek Driscoll

Fire Protection Engineering: Culminating Experience Project Reports

This project report contains a fire and life safety analysis of the Johnson Controls Office Building. The building is located in Los Angeles, California. The building is a mixed use occupancy with office spaces, meeting rooms, training rooms, and a warehouse for storing fire sprinkler and fire alarm materials. The building is one level with a mezzanine. It is attached to another building and separated by fire barrier so that they are considered separate buildings. This report contains a prescriptive analysis and a performance-based design analysis of the building.

The prescriptive code requirements were determined based on the 2019 edition …


Cal Poly Engineering Iv Building, Kai Liu Jun 2020

Cal Poly Engineering Iv Building, Kai Liu

Fire Protection Engineering: Culminating Experience Project Reports

This report analyzes the fire protection systems of Engineering IV building at California Polytechnic State University, San Luis Obispo. It is a cumulative project of the Fire Protection Engineering Program at Cal Poly. The report consists of a prescriptive analysis and a performance-based design analysis. The building contains dry laboratories, classrooms, offices, and administrative spaces. The building is a three-story structure. There is an atrium that connects the first floor to the third floor. However, the building has a horizontal enclosure to separate the connection between the second floor and the third floor.

The prescriptive analysis is based on the …


Fire Protection System Analysis Of Warren J. Baker Center Of Science And Mathematics, Jacob Dentici Jun 2019

Fire Protection System Analysis Of Warren J. Baker Center Of Science And Mathematics, Jacob Dentici

Fire Protection Engineering: Culminating Experience Project Reports

This report analyzes the different fire protection systems and features of the Warren J. Baker Center for Science and Mathematics at the California Polytechnic State University, San Luis Obispo campus. This building is used for lectures, laboratories, study spaces, faculty spaces, and storage spaces for the students and faculty at the Cal Poly campus. Typically, there are science and math courses taught within this building. The building is a 6-story structure, that is not classified as a high-rise due to the location of fire department access and has a five-story atrium located on levels 2 through 6. There are two …


Fire And Life Safety Analysis- College Campus Building, Jacob Ludeman Mar 2018

Fire And Life Safety Analysis- College Campus Building, Jacob Ludeman

Fire Protection Engineering: Culminating Experience Project Reports

A Fire and Life Safety Analysis was performed as an academic exercise as part of the MS Fire Protection Engineering Program of California Polytechnic State University, San Luis Obispo. The project is a culminating report with regards to prescriptive based and performance based aspects for the fire and life safety analysis of a project building. These analyses were performed on a building located on a college campus in Southern California and is to remain nameless upon the request of the owner and architect. The building is in the School of Physical Sciences at the University it resides. The building houses …


Taft Community College- New Student Center- Fire And Life Safety Analysis, Matthew Winston Jun 2017

Taft Community College- New Student Center- Fire And Life Safety Analysis, Matthew Winston

Fire Protection Engineering: Culminating Experience Project Reports

The following report is a fire and life safety investigation into a new facility. The planned facility is a new Student Center at Taft Community College. The prescriptive requirements as set forth by the most up to date codes and standards chosen for the project are met. The building has been properly classified with respect to occupancy and construction type. Appropriate design for interior partitions and exterior walls have been identified. Interior finish requirements are elaborated so that adherence to these guidelines is made clear. The fire sprinkler system has an adequate supply of water from the municipal water supply …


Regional Office Building- Fire And Life Safety Analysis, Peter Dwan Jun 2016

Regional Office Building- Fire And Life Safety Analysis, Peter Dwan

Fire Protection Engineering: Culminating Experience Project Reports

This report has two objectives: 1. To confirm that the Fire and Life Safety Systems of a project building satisfy applicable prescriptive code requirements, and 2. To evaluate how the Fire and Life Safety Systems perform when challenged by a credible fire scenario.

The three‐story, 31,430 sq. ft. project building is the regional office for an oil and gas company operating in Western Canada. The building includes an atrium which extends from the ground level, main floor to the third floor.

The Fire and Life Safety Systems within the scope of this study, include:

Fire Detection and Alarms Systems (FDAS) …


Culminating Project Report- Warren J. Baker Center For Science And Mathematics, Blake Johnson Mar 2015

Culminating Project Report- Warren J. Baker Center For Science And Mathematics, Blake Johnson

Fire Protection Engineering: Culminating Experience Project Reports

This report analyzes the fire protection features of the Warren J. Baker Center for Science and Mathematics on the Cal Poly San Luis Obispo campus in San Luis Obispo, CA. The prescriptive analysis of the structural fire protection, egress, fire suppression, and fire alarm, detection, and communication systems shows that the building meets the requirements of current codes and standards. The performance based analysis includes simulating design fire scenarios in the atrium using computer modeling (CFAST, FDS) and the results of these models show that the atrium meets the tenability criterion for the calculated evacuation time of occupants.


Fire Protection Analysis Of Campus Building, Mackenzie Hill Jun 2013

Fire Protection Analysis Of Campus Building, Mackenzie Hill

Fire Protection Engineering: Culminating Experience Project Reports

A prescriptive and performance based analysis has been conducted on a College Campus Building in Southern California. This building is still in the approvals process and has been designed to meet the design standards in the 2010 California Building Code (CBC) and relevant NFPA codes. The building is proposed to be the center of operations as well as having administration facilities for the College. It will house an administrative office, production and support facilities. The project is three stories and includes a balcony that does not qualify as a story. The top floor is greater than 30 feet from grade …