Air Handler Leakage: Field Testing Results In Residences, Florida Solar Energy Center, James Cummings Jan 2003

Air Handler Leakage: Field Testing Results In Residences, Florida Solar Energy Center, James Cummings

FSEC Energy Research Center®

Testing was performed to characterize air leakage in 30 air handler cabinets and at connections to supply and return ductwork. Operating pressures were measured in the air handler and plenums. Q 0.1 (Q 25) in the air handler averaged 23.9 cfm (11.3 l/s) in 30 homes. Leakage at the return and supply ductwork connections averaged 3.9 Q 0.1 (1.8 l/s Q 25) and 2.2 Q 0.1 (1.0 l/s Q 25), respectively. Actual return side leakage of 77.5 cfm (36.6 l/s) and supply side leakage of 3.1 cfm (1.5 l/s) are calculated based on Q 0.1 (Q 25) and measured operating …