Chilled ceilings

Articles 1 - 2 of 2

Full-Text Articles in Business

Energy Performance Of Indirect Evaporative Cooling In Chilled Ceiling Applications In Maritime Temperate Climates, Ben Costelloe, Donal Finn Jan 2003

Energy Performance Of Indirect Evaporative Cooling In Chilled Ceiling Applications In Maritime Temperate Climates, Ben Costelloe, Donal Finn

Conference Papers

Evaporative cooling has had limited application in maritime, temperate, climates due to the low levels of cooling water availability which result, when low temperature (5 to 8˚C), convection based, building cooling systems are used. However, the success of "high temperature" radiant cooling, in the form of chilled ceilings, has prompted a review of evaporative cooling in maritime, temperate, conditions. In order to maximize evaporative cooling availability, however, in this application, it is necessary to achieve low wet bulb temperature approach conditions, at viable levels of primary energy consumption. This paper presents the results of experimental research into the energy performance …


Evaporative Cooling Availability In Water Based Sensible Cooling Systems, Ben Costelloe, Donal Finn Sep 2001

Evaporative Cooling Availability In Water Based Sensible Cooling Systems, Ben Costelloe, Donal Finn

Conference Papers

Recent developments have prompted a review of evaporative cooling technology as an effective means of cooling modern deep plan buildings. Prominent among these developments is the success of high temperature sensible cooling systems, such as chilled ceilings, which require a supply of cooling water at 14 to 18°C. Crucial to the success of evaporative cooling technology, as a significant means of cooling in modern applications, is the ability to generate cooling water, in an indirect circuit, at a temperature which closely approaches the ambient adiabatic saturation temperature or wet bulb temperature. Recent research in this area has shown that it …