Open Access. Powered by Scholars. Published by Universities.®

Architecture Commons

Open Access. Powered by Scholars. Published by Universities.®

Articles 1 - 7 of 7

Full-Text Articles in Architecture

Sensitivity Studies Of A Low Temperature Low Approach Direct Cooling Tower For Building Radiant Cooling Systems, Medhi Nasrabadi, Donal Finn, Ben Costelloe Jul 2012

Sensitivity Studies Of A Low Temperature Low Approach Direct Cooling Tower For Building Radiant Cooling Systems, Medhi Nasrabadi, Donal Finn, Ben Costelloe

Conference Papers

Recent interest in cooling towers as a mechanism for producing chilled water, together with the evolution of radiant cooling, have prompted a review of evaporative cooling in temperate maritime climates. The thermal efficiency of such systems is a key parameter, as a measure of the degree to which the system has succeeded in exploiting the cooling potential of the ambient air. The feasibility of this concept depends largely however, on achieving low approach water temperatures within an appropriate cooling tower, at acceptable levels of energy performance. Previous experimental work for a full scale evaporative cooling system has shown that it …


Mathematical Modelling Of A Low Approach Evaporative Cooling Process For Space Cooling In Buildings, Medhi Nasrabadi, Donal Finn, Ben Costelloe Jan 2012

Mathematical Modelling Of A Low Approach Evaporative Cooling Process For Space Cooling In Buildings, Medhi Nasrabadi, Donal Finn, Ben Costelloe

Conference Papers

This paper describes a mathematical model of a low approach open evaporative cooling tower for the production of high temperature indirect cooling water (14-16°C) for use in building radiant cooling and displacement ventilation systems. There are several potential approaches to model evaporative cooling, including: the Poppe method, the Merkel method and the effectiveness-NTU (ε-NTU) method. A common assumption, applied to the Merkel and ε-NTU methods, is that the effect of change in tower water mass flow rate due to evaporation is ignored, which results in a simpler model with reduced computational requirements, but with somewhat decreasedaccuracy. In this paper, a …


Thermal Performance Of Low Approach Evaporative Cooling Systems In Buildings, Ben Costelloe, Donal Finn Apr 2006

Thermal Performance Of Low Approach Evaporative Cooling Systems In Buildings, Ben Costelloe, Donal Finn

Conference Papers

Meteorological enthalpy analysis of temperate and maritime climates above 45˚N suggests that the water-side evaporative cooling technique has considerable unrealised potential with contemporary "high temperature" building cooling systems - such as chilled ceilings. As low approach conditions are the key to exploiting the cooling potential of the ambient air, thermal performance at such conditions needs to be investigated. To address the research issues a test rig, based on an open cooling tower and plate heat exchanger and designed to maximise evaporative cooling potential, has been constructed at DIT. A combination of experimental measurement and analysis is used in the investigations. …


Thermal Efficiency Characteristics Of Indirect Evaporative Cooling Systems, Ben Costelloe, Donal Finn May 2005

Thermal Efficiency Characteristics Of Indirect Evaporative Cooling Systems, Ben Costelloe, Donal Finn

Conference Papers

Recent developments in enhancing heat transfer in cooling towers, together with the success of chilled ceilings, have prompted a review of the evaporative cooling technique. in temperate maritime climates. The thermal efficiency of such systems is a key parameter, as a measure of the degree to which the system has succeeded in exploiting the cooling potential of the ambient air. This paper presents the results of experimental research into the thermal efficiency of a water-side open indirect evaporative cooling test rig designed to achieve low (1-4 K) approach conditions. Secondary efficiencies in the range 0.24-0.76 have been achieved.


Energy Performance Of Indirect Evaporative Cooling In Chilled Ceiling Applications In Maritime Temperate Climates, Ben Costelloe, Donal Finn Jan 2003

Energy Performance Of Indirect Evaporative Cooling In Chilled Ceiling Applications In Maritime Temperate Climates, Ben Costelloe, Donal Finn

Conference Papers

Evaporative cooling has had limited application in maritime, temperate, climates due to the low levels of cooling water availability which result, when low temperature (5 to 8˚C), convection based, building cooling systems are used. However, the success of "high temperature" radiant cooling, in the form of chilled ceilings, has prompted a review of evaporative cooling in maritime, temperate, conditions. In order to maximize evaporative cooling availability, however, in this application, it is necessary to achieve low wet bulb temperature approach conditions, at viable levels of primary energy consumption. This paper presents the results of experimental research into the energy performance …


Evaporative Cooling Availability In Water Based Sensible Cooling Systems, Ben Costelloe, Donal Finn Sep 2001

Evaporative Cooling Availability In Water Based Sensible Cooling Systems, Ben Costelloe, Donal Finn

Conference Papers

Recent developments have prompted a review of evaporative cooling technology as an effective means of cooling modern deep plan buildings. Prominent among these developments is the success of high temperature sensible cooling systems, such as chilled ceilings, which require a supply of cooling water at 14 to 18°C. Crucial to the success of evaporative cooling technology, as a significant means of cooling in modern applications, is the ability to generate cooling water, in an indirect circuit, at a temperature which closely approaches the ambient adiabatic saturation temperature or wet bulb temperature. Recent research in this area has shown that it …


The Design And Performance Of An Evaporative Cooling Test Rig For A Maritime Climate, Ben Costelloe, Donal Finn Sep 2000

The Design And Performance Of An Evaporative Cooling Test Rig For A Maritime Climate, Ben Costelloe, Donal Finn

Conference Papers

Recent developments have prompted a review of the use of cooling tower based evaporative cooling technology as an effective means of cooling modern buildings. Prominent among these developments is the success of high temperature cooling systems such as radiant ceiling panels and chilled beams. At present, however, there is little published literature which gives a quantitative, in depth analysis of the performance or energy efficiency of cooling towers, used in maritime climates, in conjunction with heat exchangers and run at low approach and low wet bulb temperatures throughout the free cooling season. This lack of knowledge has meant that many …