Development Of A Desuperheater Rating Method For Energy Code Calculations, Tim Merrigan
Development Of A Desuperheater Rating Method For Energy Code Calculations, Tim Merrigan
Retrospective Theses and Dissertations
The purpose of this project was to develop a rating method for desuperheater water heaters – heat exchangers that remove superheat from the refrigerant in an air conditioner’s compressor discharge line. The project methodology was to first determine the overall heat transfer coefficient-area product (UA) of the heat exchanger for three basic types of desuperheaters. Both heat transfer analysis and the laboratory performance data indicated that the number of transfer units (NTU) for each heat exchanger was relatively independent of the operating conditions for a properly-charged air conditioner with a single-speed compressor and a desuperheater with a single-speed circulating pump. …